Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR01520
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (upstairs) | |
09/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6- Fire extinguishing systems shall be serviced annually. Last sprinkler system test was 6-14-02. | |
09/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (top of stairwell) | |
09/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 903.2.6- An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where a Group M fire area exceeds 12,000 Square feet. *With the addition and penetrations to 128 E Congress, the gross floor area is approximately 13,400 square feet. |