Case: T05FR01520

Parcel: 117150010


Addresses:

130 E CONGRESS ST


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR01520

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- The path of egress travel along a means of egress shall not be interrupted. (N exit and path, pathways throughout)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1008.1.9- Where panic and fire exit hardware are installed, the maximum unlatching force shall be 15 pounds.
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1026.17.2- For an M occupancy, the maximum travel distances are as follows:
Common Path Limit = 75 feet
Dead End Limit = 50 feet
Travel Distance to an Exit = 200 feet
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Stairwell was blocked (NW side)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Pathway to exit shall not be interrupted. (upstairs, NE stairwell)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Pathways shall not be interrupted.
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1014.2- Exits shall be unobstructed at all times. The rear (S) exit is a required exit.
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Pathways shall not be interrupted. (upstairs)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1011.1- Exits shall be marked with an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or path of egress travel is not immediately visible to the occupants.
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1006.3- In the event of a power failure, an emergency electrical system shall automatically illuminate the following areas:
1. passageways an aisles in rooms and spaceswhich require 2 or more means of egress
2. exit stairways located in buildings requiring 2 or more exits
3. interior exit discharge elements
4. the portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have 2 or more exits
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Stairwell blocked. (outside studio)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1006.3- Emergency illumination required. (music store)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1011.2- Exit signs shall be illuminated at all times. (music store)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Exit doors are blocked by piano. (music store)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1003.6- Exits shall not be blocked. (NE exit door)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1011.2- Exit signs shall be illuminated at all times. (basement)
09/26/2005 VIOL - MEANS OF EGRESS Violation TFC 1006.3- Emergency lighting for basement and stairwell is required.