Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR01520
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (N wall, several) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. A grounded application shall not be connected by means of an ungrounded adapter. (N side) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords (N side, upstairs) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Light bulb fixture shall be abated. (upstairs) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall be prohibited. | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall be prohibited. | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters shall be prohibited. | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. (studio) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. (studio) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Electrical to receptacle over doorway shall be protected. (music store) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. (electrical panel in NE corner) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3.1- Doors to electrical panel shall be marked with the words "ELECTRIC PANEL". (NE corner) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. (N window front) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4.1- Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. (small drum window) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Electrical to receptacle box shall be protected. (small drum window) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be used as permanent wiring. (S wall outside) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 603.9- Gas piping shall be protected in an approved manner. (S wall outside) | |
09/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC Extension cords shall not be used as permanent wiring. (basement) |