Permit Number: T21CM09453
Parcel: 11620637A

Address:
165 S LINDA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09453
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/27/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building permit is approved.

Stephen Blood
stephen.blood@tucsonaz.gov
05/27/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09453
165 S Linda Ave – C-2/C-3
Mixed Use Development (4th Review)

TRANSMITTAL DATE: May 27, 2022

DUE DATE: June 03, 2022

This site is located in the C-2/C-3 zone (UDC 4.7.21 & UDC 4.7.22 ). Mixed Use is an allowed use in the zone (UDC Table 4.8-4).

1. Zoning as reviewed the building plans for compliance with DP21-0157 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T21CM09453

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify code violations. Any oversight by the reviewer shall not be considered as authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The designer is responsible for following all applicable federal, state, and municipal codes and ordinances


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
19. duct over 2 stories shall be in a shaft (IMC2018,607.6.1) on sheet M4.1 Response: References to “chase” will be replaced with “shaft”. Fire smoke dampers will be added where required by 2018 IMC Section 607.5.5 and 2018 IBC Section 713.11 Not Complied the duct in question is the 5" dryer duct going up vertical to roof inside wall studs which you have not addressed. Response: We reviewed the comment with the Mechanical Plan Reviewer during a virtual meeting on April 25th. We confirmed that the dryer vents meet all the requirements of the exceptions to section 717.6.1, 2018 IBC except for #3 (maximum 4” nominal diameter). We have reduced the size of the dryer vents from 5” to 4” to meet the requirements of Exception #3 and attached the manufacturer’s installation manual for the specified dryer. Please note that all dryers will be provided with the long vent system option to exceeds the longest dryer vent provided on this project. the installation instructions for the dryer is not in the submittal's provided. please submit the installation instructions Complied
2. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
3rd Electrical Review of Bautista Apartments
Extensive revisions as shown by revision clouds
EP1.2A: Missing Keynotes 1 & 2.
EM1.6B: Several Disconnect and fuse sizes missing in HVAC Disconnect schedule.
EM1.6c: EF-Sq fuse size missing in HVAC Disconnect schedule.
EM1.6D: Cannot locate HP/S-3 in HVAC Disconnect Schedule. Do see what may be a repeat of HP/N2 (Sheet EM1.6B has very similar HP/N-2). Several Disconnect and fuse sizes missing in schedule.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov