Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM09453
Parcel: 11620637A

Address:
165 S LINDA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09453
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09453
165 S Linda Ave – C-2/C-3
Mixed Use Development (3rd Review)

TRANSMITTAL DATE: April 15, 2022

DUE DATE: April 25, 2022

This site is located in the C-2/C-3 zone (UDC 4.7.21 & UDC 4.7.22 ). Mixed Use is an allowed use in the zone (UDC Table 4.8-4).

1. Zoning as reviewed the building plans for compliance with DP21-0157 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/19/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09453

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify code violations. Any oversight by the reviewer shall not be considered as authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The designer is responsible for following all applicable federal, state, and municipal codes and ordinances.


MECHANICAL REVIEW COMMENTS:
Denied
1. guards shall be provided where appliances are within 10' of roof edge (IMC2018,304.11) on sheet M1.6 Response: Mechanical equipment has been verified and relocated where required to comply with Code Reference Section. Not Complied
10. Duct's that penetrate more than 2 stories shall be in a shaft (IMC2015,607.6.1) on sheet M2.13 Response: References to “chase” will be replaced with “shaft”. Fire smoke dampers will be added where required by 2018 IMC Section 607.5.5 and 2018 IBC Section 713.11. Complied
11. shaft penetrations shall be protected fire and smoke dampers (IMC2018,607.5.5) on sheet M2.13 Response: Fire smoke dampers will be added at shaft duct penetrations where required by 2018 IMC Section 607.5.5 and 2018 IBC Section 713.11 Complied
12. Show where your bringing in fresh ventilation air (IMC2018,106.3.1) on sheet M2.14 Response: See M2.14 and M4.5 for outside air duct routing and size. Complied
14. Mechanical systems shall not be located in an elevator shaft (IMC2018,303.8) on sheet M3.1 Response: The mechanical equipment is not located in the elevator shaft. The air conditioning unit is located adjacent to the elevator shaft. Supply and return air are ducted to and from using sidewall registers with fire smoke dampers and shaft penetration. Not Complied see correction #24
15. Provide fire and smoke dampers at all duct penetrations of shaft (IMC2018,607.5.5) on sheet M3.2 Response: Fire smoke dampers have been provided at all shaft wall penetrations. Not Complied you don't have the fire and smoke dampers where ducts penetrates the shaft on M3.2 on your revised plans.
16. Mechanical systems shall not be installed in an elevator shaft (IMC2018,303.8) on sheet M3.4 Response: The mechanical equipment is not located in the elevator shaft. The air conditioning unit is located adjacent to the elevator shaft. Supply and return air are ducted to and from using sidewall registers with fire smoke dampers and shaft penetration. Not Complied see correction #24
17. Appliances installed in fire rated assembly shall be protected in an approved manner (IMC2018,303.2) on sheet M4.1 Response: Mechanical equipment is located above the fire rated ceiling. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied
18. Provide radiation dampers at diffusers penetrating fire rated ceiling assembly (IMC2018,607.6.2) on sheet M4.1 Response: Air devices are located above the fire rated ceiling. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied
19. duct over 2 stories shall be in a shaft (IMC2018,607.6.1) on sheet M4.1 Response: References to “chase” will be replaced with “shaft”. Fire smoke dampers will be added where required by 2018 IMC Section 607.5.5 and 2018 IBC Section 713.11 Not Complied the duct in question is the 5" dryer duct going up vertical to roof inside wall studs which you have not addressed.
20. Provide radiation dampers (IMC2018,607.6.2) on sheet M4.1 Response: Air devices are located above the fire rated ceiling. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied
21. Appliances installed in fire rated assembly shall be protected in an approved manner (IMC2018,303.2) on sheet M4.1 Response: Mechanical equipment is located above the fire rated ceiling. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied
22. Provide radiation dampers at all ceiling penetrations (IMC2018,607.6.2)on sheet M4.1 Response: Air devices are located below the fire rated ceiling. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied
24. Mechanical systems shall not be installed in an elevator shaft (IMC2018,303.8) on sheet M3.3 Response: The mechanical equipment is not located in the elevator shaft. The air conditioning unit is located adjacent to the elevator shaft. Supply and return air are ducted to and from using sidewall registers with fire smoke dampers and shaft penetration. Not Complied You will need a letter from the ICC, to clarify this as I see no exception to this code section, and furthermore IBC2018,3002.9 specifically prohibits mechanical system from being installed in elevator hoist way's. you will need a letter from the ICC for a judgement call.
28. Mechanical systems shall not be installed in an elevator shaft (IMC2018,303.8) on sheet M3.3 Response: The mechanical equipment is not located in the elevator shaft. The air conditioning unit is located adjacent to the elevator shaft. Supply and return air are ducted to and from using sidewall registers with fire smoke dampers and shaft penetration. Not Complied see correction #24
29. Show where you are bringing in ventilation air (IMC2018,106.3.1) on sheet M4.5 Response: See M2.14 and M4.5 for outside air duct routing and size. Complied
34. Provide ceiling radiation dampers (IMC2018,607.6.2) on sheet M4.7 Response: Air devices are located below the fire rating. Refer to architects reflected ceiling plans (series A2 in the architectural set) for fire rating type and location. Complied


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
EP1.2A: Missing Keynotes 1 & 2.
EM1.6B: Several Disconnect and fuse sizes missing in HVAC Disconnect schedule.
EM1.6c: EF-Sq fuse size missing in HVAC Disconnect schedule.
EM1.6D: Cannot locate HP/S-3 in HVAC Disconnect Schedule. Do see what may be a repeat of HP/N2 (Sheet EM1.6B has very similar HP/N-2). Several Disconnect and fuse sizes missing in schedule.


PLUMBING REVIEW COMMENTS:
Denied
Third Review:
1). Updated Civil page sheet 9 doesn't show the connection to 16" storm drain lateral as shown on plan P1.0, also sheet 10 not sent to see the size of the storm sewer that these 10" & 16" storm laterals are connecting to. -IPC 1106.2 2 thru 8 OK
9). Bottom of plan page P1.0 the 219 DFU BLDG drain is labeled 6" & 4"? If it is 4" then it is undersized. -IPC 710.1 10 thru 15 OK
16). Now that the public area waste/vent risers have been added to plan page P6.5 the following needs to be revised:
Detail #1 Both P-2A toilets need circuit vents,
Detail #2 The three toilets grouped together need to have their circuit vent located so that the most upstream toilet drains pass it.
Detail #3 needs 2 circuit vents added on main trunk line between fixtures 7 & 8 and between the most upstream toilet & triple lav branch connection. -IPC 914
17 thru 29 OK
30). Same- Elevator sump detail #2 needs shut off valve on discharge side of check valve. IPC 712.2
31 thru 35 OK
36). Now that the piping materials have been added to plan page P8.2 update the underground piping notes to comply with -
IFGG 404.11.2
37). OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/11/2022 JPEELDA1 FIRE REVIEW Approved
05/13/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building permit is approved.

Stephen Blood
stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2022 DBENOIT1 APPROVAL SHELF Completed
05/13/2022 DBENOIT1 OUT TO CUSTOMER Completed
05/13/2022 DBENOIT1 REJECT SHELF Completed