Permit Number: T17CM00004
Parcel: 12404097C

Address:
950 N TYNDALL AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T17CM00004
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2017 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
03/22/2017 MARTIN BROWN FIRE REVIEW Reqs Change pending review of stantecs comments
03/22/2017 MARTIN BROWN FIRE REVIEW Reqs Change Fire completed first review and waiting for resubmittal to verify compliance with Stantec comments
03/23/2017 SSHIELD1 ADA REVIEW Passed
03/23/2017 LOREN MAKUS ENGINEERING REVIEW Passed
03/23/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 950 N. Tyndall Avenue
T17CM00004
Building Plan (1st Review)

TRANSMITTAL DATE: March 23, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the parapet shown at the northwest corner of the building exceeds the allowed 4'-0" height see LUC Section 3.2.7.3.E.

3. The building plans must be approved and stamped by the design professional prior to approval by zoning.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
03/27/2017 CLAURIE1 DESIGN PROFESSIONAL REVIEW Reqs Change Plan review for compatibility of permit elevations to approved design package elevations:

Plan sheets reviewed
A09.001 East Elevation
A09.002 North Elevation
A09.003 West Elevation
A09.004 South Elevation

Elevations are not compatible with the design package.

The minor exception was on the East Elevation- the double doors were replaced with a roll door, and at the center of the elevation, the design was changed from stucco to brick.

Final plan elevations to be reviewed for consistancy.
09/18/2017 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
09/18/2017 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2017 FERNE RODRIGUEZ OUT TO CUSTOMER Completed