Permit: TC-RES-0925-04449
Permit Details
Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
5672 E ALTA VISTA ST UNIT 2
Address NEW:
5672 E ALTA VISTA ST UNIT 2
Apply Date:
09/09/2025
Applicant:
Jason Ayler
Description:
Convert Detached Building into ADU with Bathroom Addition
Permit Reviews
Permit Number - TC-RES-0925-04449
Permit Status: Inspections
Permit Description: Convert Detached Building into ADU with Bathroom Addition
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/02/2026 | RESIDENTIAL ADU v.4 | 01/15/2026 | REQUIRES RESUBMIT |
| 09/12/2025 | RESIDENTIAL ADU v.1 | 10/16/2025 | REQUIRES RESUBMIT |
| 05/14/2026 | ADMINISTRATIVE v.1 | N/A | REQUIRES RESUBMIT |
| 11/24/2025 | RESIDENTIAL ADU v.2 | 12/05/2025 | REQUIRES RESUBMIT |
| 02/13/2026 | RESIDENTIAL ADU v.5 | 02/13/2026 | REQUIRES RESUBMIT |
| 02/20/2026 | RESIDENTIAL ADU v.6 | 03/13/2026 | REQUIRES RESUBMIT |
| 12/22/2025 | RESIDENTIAL ADU v.3 | 12/22/2025 | REQUIRES RESUBMIT |
| 05/04/2026 | RESIDENTIAL ADU v.7 | N/A | APPROVED |
Conditions
Permit Number - TC-RES-0925-04449
Permit Status: Inspections
Permit Description: Convert Detached Building into ADU with Bathroom Addition
| Date | Description | Comments |
|---|---|---|
| 09/12/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-RES-0925-04449
Permite Description: Convert Detached Building into ADU with Bathroom Addition
Total Outstanding Inspections - 11
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2026 | COT - RSBU - Excavation/Rebar/Zoning | N/A | Not Applicable | |
| 07/02/2026 | RSBU - Building Final | N/A | Re-inspection required | 7.2.26 1. Subpanel needs minimum of 36" clearance in front 2. Need 2 small appliance circuit in kitchen on 20A breakers GFCI protected 3. Bathroom receptacles need to be GFCI protected 4. Mini Split is not UL listed. 5. Water heater needs t/p line terminating to a pan or ground 2"-6". 6. Label all circuits and create panel schedule. 7. Water hammer arrestors needed at laundry washer. |
| 07/02/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Not Applicable | |
| 07/02/2026 | COT - RSBU - Preslab | N/A | Not Applicable | |
| 07/02/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Not Applicable | |
| 07/02/2026 | COT - RSBU - Roof Nailing | N/A | Not Applicable | |
| 07/02/2026 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 7.2.26 1. Subpanel needs minimum of 36" clearance in front 2. Need 2 small appliance circuit in kitchen on 20A breakers GFCI protected 3. Bathroom receptacles need to be GFCI protected 4. Mini Split is not UL listed. 5. Water heater needs t/p line terminating to a pan or ground 2"-6". 6. Label all circuits and create panel schedule. |
| 07/02/2026 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 7.2.26 1. Subpanel needs minimum of 36" clearance in front 2. Need 2 small appliance circuit in kitchen on 20A breakers GFCI protected 3. Bathroom receptacles need to be GFCI protected 4. Mini Split is not UL listed. 5. Water heater needs t/p line terminating to a pan or ground 2"-6". 6. Label all circuits and create panel schedule. 7. Water hammer arrestors needed at laundry washer. |
| 07/02/2026 | COT - RSPL - Yard Water Line | N/A | Not Applicable | |
| 07/02/2026 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 7.2.26 1. Subpanel needs minimum of 36" clearance in front 2. Need 2 small appliance circuit in kitchen on 20A breakers GFCI protected 3. Bathroom receptacles need to be GFCI protected 4. Mini Split is not UL listed. 5. Water heater needs t/p line terminating to a pan or ground 2"-6". 6. Label all circuits and create panel schedule. 7. Water hammer arrestors needed at laundry washer. |
| 07/02/2026 | COT - RSPL - Rough Soil | N/A | Not Applicable |