Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical FinalĀ
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2026 | COT - RSME - Mechanical FinalĀ | Re-inspection required | 7.2.26 1. Subpanel needs minimum of 36" clearance in front 2. Need 2 small appliance circuit in kitchen on 20A breakers GFCI protected 3. Bathroom receptacles need to be GFCI protected 4. Mini Split is not UL listed. 5. Water heater needs t/p line terminating to a pan or ground 2"-6". 6. Label all circuits and create panel schedule. 7. Water hammer arrestors needed at laundry washer. |