Permit: TC-RES-0524-02761
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
6502 E SHEPHERD HILLS
Address NEW:
6502 E SHEPHERD HILLS
Apply Date:
05/06/2024
Applicant:
Hailey McGraw
Description:
ROOF MOUNTED PV SYSTEM 16.8kW DC / 11.5kW AC REV 3: MPU TO 225A/200A PANEL
Permit Reviews
Permit Number - TC-RES-0524-02761
Permit Status: Complete
Permit Description: ROOF MOUNTED PV SYSTEM
16.8kW DC / 11.5kW AC
REV 3: MPU TO 225A/200A PANEL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/10/2024 | RESIDENTIAL SOLAR v.1 | 06/24/2024 | APPROVED |
| 01/10/2025 | RESIDENTIAL SOLAR REVISION v.1 | 01/28/2025 | APPROVED |
| 05/06/2024 | RESIDENTIAL SOLAR v.1 | 06/04/2024 | APPROVED |
| 07/11/2025 | RESIDENTIAL SOLAR REVISION v.1 | 08/08/2025 | APPROVED |
| 09/03/2024 | RESIDENTIAL SOLAR REVISION v.1 | 09/18/2024 | APPROVED |
Conditions
Permit Number - TC-RES-0524-02761
Permit Status: Complete
Permit Description: ROOF MOUNTED PV SYSTEM
16.8kW DC / 11.5kW AC
REV 3: MPU TO 225A/200A PANEL
| Date | Description | Comments |
|---|---|---|
| 01/27/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-0524-02761
Permite Description: ROOF MOUNTED PV SYSTEM
16.8kW DC / 11.5kW AC
REV 3: MPU TO 225A/200A PANEL
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2025 | BULD - Electrical Clearance | N/A | Re-inspection required | 7.3.25 No lineside tap, system is not per plans. Instead a 60A backfeed breaker is installed. Either submit a revision or install according to plans. |
| 07/03/2025 | RSBU - Building Final | N/A | Re-inspection required | 7.3.25 No lineside tap, system is not per plans. Instead a 60A backfeed breaker is installed. Either submit a revision or install according to plans. |
| 07/03/2025 | COT - RSOL - Electrical Final Solar Project | N/A | Re-inspection required | 7.3.25 No lineside tap, system is not per plans. Instead a 60A backfeed breaker is installed. Either submit a revision or install according to plans. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0524-02761
Permit Description: ROOF MOUNTED PV SYSTEM
16.8kW DC / 11.5kW AC
REV 3: MPU TO 225A/200A PANEL
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2025 | BULD - Electrical Clearance | Passed | REVISED PLANS VERIFIED. PV SYSTEM INSTALLED PER REVISED PLANS. APPROVED DGC/BAT |
|
| 08/14/2025 | RSBU - Building Final | Passed | 8.14.25 REVISED PLANS VERIFIED. PV SYSTEM INSTALLED PER REVISED PLANS. APPROVED DGC/BAT |
|
| 08/14/2025 | COT - RSOL - Electrical Final Solar Project | Passed | 8.14.25 REVISED PLANS VERIFIED. PV SYSTEM INSTALLED PER REVISED PLANS. APPROVED DGC/BAT |