Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSOL - Electrical Final Solar Project
Permit Number - TC-RES-0524-02761
Inspection Description - COT - RSOL - Electrical Final Solar Project
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2025 | COT - RSOL - Electrical Final Solar Project | Re-inspection required | 7.3.25 No lineside tap, system is not per plans. Instead a 60A backfeed breaker is installed. Either submit a revision or install according to plans. |
|
| 07/09/2025 | COT - RSOL - Electrical Final Solar Project | Re-inspection required | Failed, installation not per approved plans on file, please revise plans and submit for approval | |
| 08/14/2025 | COT - RSOL - Electrical Final Solar Project | Passed | 8.14.25 REVISED PLANS VERIFIED. PV SYSTEM INSTALLED PER REVISED PLANS. APPROVED DGC/BAT |