Permit Details

Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
3042 S TOWER RD
Address NEW:
3042 S TOWER RD
Apply Date:
01/27/2026
Applicant:
Fernando Hinojosa
Description:
New Detached sleeping quarters.

Permit Reviews

Permit Number - TC-RES-0126-00429
Permit Status: Inspections
Permit Description: New Detached sleeping quarters.
Start Date Submittal Complete Date Status  
03/31/2026 ADMINISTRATIVE v.1 N/A REQUIRES RESUBMIT Review Details
03/16/2026 RESIDENTIAL ADD/ALT v.2 03/31/2026 APPROVED Review Details
02/03/2026 RESIDENTIAL ADD/ALT v.1 02/20/2026 REQUIRES RESUBMIT Review Details
03/31/2026 ADMINISTRATIVE v.2 N/A APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-RES-0126-00429
Permit Status: Inspections
Permit Description: New Detached sleeping quarters.
Total Outstanding Activity Conditions - 1
Date Name
02/17/2026 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Conditions

Permit Number - TC-RES-0126-00429
Permit Status: Inspections
Permit Description: New Detached sleeping quarters.
Date Description Comments
02/03/2026 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-RES-0126-00429
Permite Description: New Detached sleeping quarters.
Total Outstanding Inspections - 7
Last Inspection Date Description Inspector Results Comments
07/19/2026 COT - RSPL - Rough Soil N/A Re-inspection required 7/17/26: Sewer line is running parallel to footing within the 45 degree bearing plane. Rough soil will need to be re-done and have approved fittings and have appropriate slope for discharge. Areas that were not exposed will need to be snaked with cameras verify slope and fitting directions, multiple fittings in wall not installed in correct position. Boca plates required throughout where plumbing/mechanical/electrical come within 1 1/4" from face of stud. All penetrations at top plate must be properly sealed, over notched studs must be addressed, over notched top plates must be addressed, properly support DWV in wall and above ceiling, properly support pex lines, fully expose sewer connection outside of home, permit required for laundry room sewer run
05/22/2026 COT - RSBU - Roof Nailing N/A Re-inspection required 5-22-26: This job relates to a Code Enforcement Case/ Building without permits-provide truss calculations, add anchor bolts are marked locations, tighten all anchor bolts, anchor bolts are required within 12" at the end each exterior plate and 2 anchor bolts are required within 12" on each side of a splice, add shot pins to marked locations, provide a letter from a licensed contractor documenting exterior sheathing together with roof nailing was done per plans & meets the 2024 IRC-submit letter to the city as an attachment for review & approval, missing backing at the restroom. See the City of Tucson Inclusive page for bracing/backing requirements & add backing at restroom. Stopped inspection-additional items may be added.
05/22/2026 COT - RSPL - Yard Water Line N/A Re-inspection required 5-22-26: expose underground water line so that we may verify proper depth, tracer wire, proper installation, and water line must be tested under pressure.
05/22/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing N/A Re-inspection required 5-22-26: This job relates to a Code Enforcement Case/ Building without permits-provide truss calculations, add anchor bolts are marked locations, tighten all anchor bolts, anchor bolts are required within 12" at the end each exterior plate and 2 anchor bolts are required within 12" on each side of a splice, add shot pins to marked locations, provide a letter from a licensed contractor documenting exterior sheathing together with roof nailing was done per plans & meets the 2024 IRC-submit letter to the city as an attachment for review & approval, missing backing at the restroom. See the City of Tucson Inclusive page for bracing/backing requirements & add backing at restroom. Stopped inspection-additional items may be added.
05/22/2026 COT - RSPL - Sewer N/A Re-inspection required 5-22-26: expose pockets throughout exterior underground plumbing to verify piping, tracer wire, excavation depth. For all underground plumbing underneath slab a snake with camera will be required to verify proper flow and contains no blockages. A certified licensed plumber is required to perform test. Provide all results/ reports upon re-inspection and upload them to the city for review. Expose sewer for same. All underground plumbing together with sewer requires a pressure test.
05/22/2026 COT - RSBU - Excavation/Rebar/Zoning N/A Re-inspection required 5-22-26: provide any pictures/videos which documents reinforcement, an X-Ray of reinforcement under the slab must be completed by a company who specializes in this field. Those reports must be submitted to the city for review/approval & expose pockets throughout exterior footings to verify depth.
10/14/2026 COT - RSBU - Interior Shear Bracing N/A Partial Pass Partial pass. Drywall shall reach the bottom plate and fastened. Drywall screws shall not be closer to the edges of a minimum of 3/8". Ensure all boxes are cut out. 10/14/2026

Completed Inspections

Permit Status: Inspections
Permit Number: TC-RES-0126-00429
Permit Description: New Detached sleeping quarters.
Total Completed Inspections - 8
Date Description Inspector Results Comments
07/30/2026 COT - RSPL - Rough Soil Passed 7/30/26: Plumbing underground approved. Please ensure Preslab inspection is called in for pour backs at sawcut locations.
09/29/2026 COT - RSBU - Roof Nailing Passed
09/29/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed
09/29/2026 COT - RSPL - Yard Water Line Passed
09/29/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
09/29/2026 COT - RSPL - Sewer Passed
09/29/2026 COT - RSBU - Excavation/Rebar/Zoning Passed
10/15/2026 COT - RSBU - Interior Shear Bracing Passed