Permit: TC-RES-0123-02498
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
729 E 35TH ST
Address NEW:
729 E 35TH ST
Apply Date:
01/31/2023
Applicant:
alex enoch
Description:
Duplex
Permit Reviews
Permit Number - TC-RES-0123-02498
Permit Status: Complete
Permit Description: Duplex
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/31/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 11/05/2024 | REQUIRES RESUBMIT |
| 12/14/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/03/2025 | APPROVED |
| 02/03/2025 | RESIDENTIAL NEW DWELLING REVISION v.1 | 03/07/2025 | REQUIRES RESUBMIT |
| 05/04/2023 | RESTAMP - RESIDENTIAL v.1 | 05/04/2023 | APPROVED |
| 09/18/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/18/2024 | REQUIRES RESUBMIT |
| 04/06/2023 | RESIDENTIAL NEW DWELLING v.2 | 05/04/2023 | APPROVED |
| 03/01/2023 | RESIDENTIAL NEW DWELLING v.1 | 03/30/2023 | REQUIRES RESUBMIT |
| 04/02/2025 | RESIDENTIAL NEW DWELLING REVISION v.2 | 04/29/2025 | APPROVED |
| 04/29/2025 | RESTAMP - RESIDENTIAL v.1 | 04/30/2025 | APPROVED |
| 11/08/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.3 | 11/12/2024 | APPROVED |
Conditions
Permit Number - TC-RES-0123-02498
Permit Status: Complete
Permit Description: Duplex
| Date | Description | Comments |
|---|---|---|
| 11/08/2024 | Compaction AND FILLING IS REQUIRED. | |
| 05/04/2023 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/integrated-planning/PDSD/PDSD_Owner_Builder_Affidavit.pdf, is required prior to issuance of permit. | |
| 11/08/2024 | Architect submitted 11/8/24 | |
| 11/08/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 08/19/2024 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-0123-02498
Permite Description: Duplex
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2024 | COT - RSEL - Grounding/Bonding | N/A | Partial Pass | 12-17-24, partial pass for UFER. |
| 12/17/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Partial Pass | 12-17-24, carport still pending. Unit 1 clips/sheathing approved-Okay to continue construction.Unit 2, add shot pins to marked locations and an anchor bolt on west side.Reinspection required. |
| 06/17/2025 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
| 12/30/2024 | BULD - Electrical Clearance | N/A | Not Ready | 12/30/24: Hold on Permit must be addressed prior to any further inspection being called in. |
| 12/17/2024 | COT - RSBU - Excavation/Rebar/Zoning | N/A | Partial Pass | 10/15/24: reinforcement per plans at slab for home and patio ok to proceed. Pending car port. 11/27/24: Anchor bolts required to be 1/2" in size (currently installed are 3/8"), anchor bolts required 48" o.c at fire wall, anchor bolts required 12" from edge of sill plate, hold downs missing per plans at south west corner of duplex at unit 1, fire block required at west and east wall of fire wall, no roof access, please provide truss clacs, 3-10D nails required at ledger every stud, truss cannot be closer then 3" from splice of top plate, |
| 06/18/2025 | COT - RSEL - Outdoor Lighting | N/A | Re-inspection required | 6-18-25: paint all exterior plastic including any plastic on rooftops, seal both water closets, lower thermostat height to 48" o.c., install light bulb on exterior light fixture. Unit 2-install anti-tip device at stove, lower thermostat to 48" o.c., paintball exterior plastic, seal both water closets, insulate copper hose bibs, and wrap using 10 mil tape, provide an updated panel schedule for unit 2-showing disposal. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0123-02498
Permit Description: Duplex
Total Completed Inspections - 19