Permit: TC-RES-0123-02498

Parcel: 129132920


Addresses:

729 E 35TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
11/27/2024 COT - RSBU - Roof NailingĀ  Re-inspection required 10/15/24: reinforcement per plans at slab for home and patio ok to proceed. Pending car port.
11/27/24: Anchor bolts required to be 1/2" in size (currently installed are 3/8"), anchor bolts required 48" o.c at fire wall, anchor bolts required 12" from edge of sill plate, hold downs missing per plans at south west corner of duplex at unit 1, fire block required at west and east wall of fire wall, no roof access, please provide truss clacs, 3-10D nails required at ledger every stud, truss cannot be closer then 3" from splice of top plate,
12/17/2024 COT - RSBU - Roof NailingĀ  Passed 12-17-24, roof nailing for units 1 & 2 approved. Okay to continue construction on roof.