Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2025 | COT - RSBU - Excavation/Rebar/Zoning | Passed | ||
| 10/15/2024 | COT - RSBU - Excavation/Rebar/Zoning | Partial Pass | 10/15/24: reinforcement per plans at slab for home and patio ok to proceed. Pending car port. | |
| 11/27/2024 | COT - RSBU - Excavation/Rebar/Zoning | Partial Pass | 10/15/24: reinforcement per plans at slab for home and patio ok to proceed. Pending car port. 11/27/24: Anchor bolts required to be 1/2" in size (currently installed are 3/8"), anchor bolts required 48" o.c at fire wall, anchor bolts required 12" from edge of sill plate, hold downs missing per plans at south west corner of duplex at unit 1, fire block required at west and east wall of fire wall, no roof access, please provide truss clacs, 3-10D nails required at ledger every stud, truss cannot be closer then 3" from splice of top plate, |
|
| 12/17/2024 | COT - RSBU - Excavation/Rebar/Zoning | Partial Pass | 12-17-24, Setbacks verified for units, however, still pending carport framing. |