Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
8650 S ALVERNON WY
Apply Date:
09/02/2025
Applicant:
Ian Regan
Description:
Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00

Permit Reviews

Permit Number - TC-COM-0925-01611
Permit Status: Issued
Permit Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Start Date Submittal Complete Date Status  
04/27/2026 SPECIAL INSPECTION REVIEW v.1 04/29/2026 APPROVED Review Details
01/23/2026 COMMERCIAL REVIEW - LIMITED v.3 02/09/2026 REQUIRES RESUBMIT Review Details
09/30/2025 COMMERCIAL REVIEW - LIMITED v.2 10/21/2025 REQUIRES RESUBMIT Review Details
09/04/2025 COMMERCIAL REVIEW - LIMITED v.1 09/22/2025 REQUIRES RESUBMIT Review Details
04/06/2026 ADMINISTRATIVE v.1 04/06/2026 REQUIRES RESUBMIT Review Details
03/05/2026 COMMERCIAL REVIEW - LIMITED v.4 03/25/2026 APPROVED Review Details
04/27/2026 ADMINISTRATIVE v.2 N/A IN REVIEW Review Details
06/26/2026 SPECIAL INSPECTION REVIEW v.1 06/29/2026 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0925-01611
Permit Status: Issued
Permit Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Total Outstanding Activity Conditions - 4
Date Name
04/28/2026 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
04/28/2026 Post-Installed Anchor Inspection Report is required.
04/28/2026 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.
06/29/2026 Special inspections must be performed by an approved third party inspection agency at the owner's expense. Special inspection forms and reports are required to be submitted for review and approved prior to issuance of final approval documents.

Conditions

Permit Number - TC-COM-0925-01611
Permit Status: Issued
Permit Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Date Description Comments
09/19/2025 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
09/04/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
09/04/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
09/19/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0925-01611
Permite Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
06/03/2026 COT - LCEL - Grounding/Bonding N/A Partial Pass 6/3/26: #3/0 ground from electrical system grd bus to test stand pad#1 per approved plans, #3/0 ground from SWGR to test stand pad #2 per approved plans ok to proceed with backfill.
06/26/2026 COT - LCEL - Electrical Underground N/A Partial Pass 6-26-26: verified 4 electrical schedule 40 conduit stub-ups to pull boxes and a total of 4 Caldwell grounds (3/0 ) to reinforcement on future slab on grade. 2 grounds at reinforcement located at the northeast section and the other set located near the center of slab. Okay to backfill progress areas using shading materials.
07/01/2026 COT - LCBU - Excavation/Rebar/Zoning N/A Re-inspection required 7-1-26: called POC at 723am and left message advising that I would be on site in the next 5 minutes. Arrived on site at 727am and waited for an escort at Gate 81A. I waited until 737am and left. Reschedule inspection when ready.
Note: another failed inspection will result with a re-inspection fee.
06/08/2026 COT - LCBU - Preslab N/A Partial Pass 6/8/26: GL 1 and 3 ready for concrete placement ( submit revised set of plans on DP to accurately reflect 5" Concrete over 4" ABC)

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0925-01611
Permit Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/14/2026 PDSD Building Division Pre-Construction Meeting Passed

Scheduled Inspections

Scheduled Inspections - TC-COM-0925-01611
Status: Issued
Description: Construction of Outdoor Concrete Equipment Test Pad - Ref.: TD-DEV-0325-00075 3500000.00
Scheduled Date Description Entered By Entered Date
07/02/2026 COT - LCBU - Preslab Scheduled
For information about today’s scheduled inspections please refer to the PDSD Daily Inspections Dashboards (Desktop) PDSD Daily Inspections Dashboards (Mobile) .

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
SPECIAL_INSPECTION_CERTIFICATE, RAYTHEON RTX TEST STAND, FIRST STAMP-2026-04-21_V1.PDF DOCUMENTS VIEW
CONS-TC-COM-0925-01611-REV-2-26-0114_V2.PDF DOCUMENTS VIEW
SPAPP-RESUBMISSION-RESPONSE LETTER-26-0304-2026-03-05_V1.PDF DOCUMENTS VIEW