Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Commercial Building
Address NEW:
10080 E OLD VAIL RD
Apply Date:
05/08/2025
Applicant:
Ethan Epling
Description:
THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.

Permit Reviews

Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Start Date Submittal Complete Date Status  
09/15/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 09/19/2025 APPROVED Review Details
09/19/2025 ADMINISTRATIVE v.2 09/19/2025 APPROVED Review Details
09/11/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 09/12/2025 APPROVED Review Details
09/12/2025 ADMINISTRATIVE v.1 09/12/2025 REQUIRES RESUBMIT Review Details
08/08/2025 COMMERCIAL REVIEW - FULL v.3 08/18/2025 APPROVED Review Details
08/18/2025 RESTAMP - COMMERCIAL v.1 08/20/2025 APPROVED Review Details
07/10/2025 COMMERCIAL REVIEW - FULL v.2 07/31/2025 REQUIRES RESUBMIT Review Details
05/13/2025 COMMERCIAL REVIEW - FULL v.1 06/09/2025 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Total Outstanding Activity Conditions - 7
Date Name
08/18/2025 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
08/18/2025 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
08/18/2025 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
08/18/2025 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
08/18/2025 SPECIAL INSPECTION FOR WELDING IS REQUIRED.
08/18/2025 SPECIAL INSPECTION FOR WOOD FRAMED DIAPHRAGMS AND SHEAR WALLS IS REQUIRED.
09/12/2025 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.

Conditions

Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Date Description Comments
05/13/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
07/31/2025 Separate submittal to PC Industrial Wastewater Control is required for dental offices, dental schools and clinics. Contact Kelsey.McMonagle@pima.gov for review and assessment of compliance with the rules for amalgam separators.
08/18/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0525-00942
Permite Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
10/02/2025 COT - HCPL - Rough Soil N/A Partial Pass 10-2-25: partial pass pending sewer/ water. Underground plumbing on DWV verified per plans-okay to backfill progress areas with shading materials.
10/03/2025 COT - LCPL - Yard Water Line N/A Not Ready
11/07/2025 COT - HCBU - Preslab N/A Partial Pass 11-7-25: 10 mil vapor retarder in place-okay to pour slab.
11/28/2025 For trash and recycling enclosures N/A Not Ready Called, Ethan Epling, phone number: (520) 730-0197. Drove to site no access and no activity.
11/28/2025 COT - HCEL - Electrical Underground N/A Re-inspection required 11/28/25
LIGHT POLES:
1. West light pole is missing spare 3/4" stub out; Rebar clearance needs to be 3" minimum from earth, very little clearance on the sides.
2. South light pole caisson rebar sitting on the ground; Sonos tube installed upside down.
3. East light pole, 3" clearance needed on the sides for Rebar from earth and Sonos tube installed upside down.
12/16/2025 COT - HCEL - Outdoor Lighting N/A Partial Pass 12/16/25
Needed Electrical underground for exterior lighting; Ok to backfill.
12/18/2025 COT - HCME - Mechanical Above Ceiling N/A Partial Pass Partial pass for paddy, ok to wrap and insulate
12/23/2025 COT - HCBU - Building Progress N/A Partial Pass 12/23/25: wire and lathe inspection
01/09/2026 COT - HCPL - Plumbing Progress N/A Partial Pass Partial pass. Inspection is for wall approved for both DWV and domestic water lines. Isolators were mentioned for PVC running through metal studs. Possible leak at north end center of building above ceiling. Re pressurize system prior to next inspection. 1/9/2026
01/12/2026 COT - HCPL - Plumbing Above Ceiling N/A Re-inspection required 1/12/26: Per IPC table 308.5 horizontal supports on PVC is required 4’ o.c. (Supports over spaced throughout above ceiling and in wall), Per table 308.5 copper 1 1/4” or smaller required to have supports 6’ o.c at horizontal supports, properly secure copper piping throughout, R-3 insulation required at hot water piping 3/4” or larger, per previous notes
01/06/2026 COT - HCEL - Electrical Progress N/A Partial Pass 1/6/26: electrical in-wall approved for rough-ins.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-COM-0525-00942
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Total Completed Inspections - 6
Date Description Inspector Results Comments
10/03/2025 COT - HCPL - Sewer Passed
10/28/2025 COT - HCBU - Excavation/Rebar/Zoning Passed Passed 10/28/25 ok to pour concrete
12/05/2025 COT - HCBU - Roof Nailing Passed Passed 12/5/25 nailing per plans
12/05/2025 COT - HCBU - Exterior Clips/Sheathing Passed Passed 12/5/25 nailing per plans
12/05/2025 COT - HCBU - Framing Passed Passed 12/5/25 nailing per plans
01/14/2026 BULD - Electrical Clearance Passed 1/14/26:ECO TEP CLEARANCE 10080 E OLD VAIL RD

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
NOI-NDC PERMIT_V1.PDF DOCUMENTS VIEW
SPECIAL_INSPECTION_CERTIFICATE-2025-09-10_V1.PDF DOCUMENTS VIEW
CONS-HEARTLAND DENTAL TUCSON AZ_DRAWINGS REV 2_V3.PDF DOCUMENTS VIEW