Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-0525-00942
Permit Details
Status:
Inspections
Type:
Commercial Building
Address:
10080 E OLD VAIL RD
Address NEW:
10080 E OLD VAIL RD
Apply Date:
05/08/2025
Applicant:
Ethan Epling
Description:
THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE LISTED BELOW.
Permit Reviews
Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE
INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD
FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD
FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE
LISTED BELOW.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/15/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/19/2025 | APPROVED |
| 09/19/2025 | ADMINISTRATIVE v.2 | 09/19/2025 | APPROVED |
| 09/11/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/12/2025 | APPROVED |
| 09/12/2025 | ADMINISTRATIVE v.1 | 09/12/2025 | REQUIRES RESUBMIT |
| 08/08/2025 | COMMERCIAL REVIEW - FULL v.3 | 08/18/2025 | APPROVED |
| 08/18/2025 | RESTAMP - COMMERCIAL v.1 | 08/20/2025 | APPROVED |
| 07/10/2025 | COMMERCIAL REVIEW - FULL v.2 | 07/31/2025 | REQUIRES RESUBMIT |
| 05/13/2025 | COMMERCIAL REVIEW - FULL v.1 | 06/09/2025 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE
INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD
FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD
FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE
LISTED BELOW.
Total Outstanding Activity Conditions - 7
| Date | Name |
|---|---|
| 08/18/2025 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
| 08/18/2025 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. |
| 08/18/2025 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 08/18/2025 | SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED. |
| 08/18/2025 | SPECIAL INSPECTION FOR WELDING IS REQUIRED. |
| 08/18/2025 | SPECIAL INSPECTION FOR WOOD FRAMED DIAPHRAGMS AND SHEAR WALLS IS REQUIRED. |
| 09/12/2025 | SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED. |
Conditions
Permit Number - TC-COM-0525-00942
Permit Status: Inspections
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE
INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD
FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD
FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE
LISTED BELOW.
| Date | Description | Comments |
|---|---|---|
| 05/13/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 07/31/2025 | Separate submittal to PC Industrial Wastewater Control is required for dental offices, dental schools and clinics. Contact Kelsey.McMonagle@pima.gov for review and assessment of compliance with the rules for amalgam separators. | |
| 08/18/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-COM-0525-00942
Permite Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE
INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD
FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD
FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE
LISTED BELOW.
Total Outstanding Inspections - 11
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2025 | COT - HCPL - Rough Soil | N/A | Partial Pass | 10-2-25: partial pass pending sewer/ water. Underground plumbing on DWV verified per plans-okay to backfill progress areas with shading materials. |
| 10/03/2025 | COT - LCPL - Yard Water Line | N/A | Not Ready | |
| 11/07/2025 | COT - HCBU - Preslab | N/A | Partial Pass | 11-7-25: 10 mil vapor retarder in place-okay to pour slab. |
| 11/28/2025 | For trash and recycling enclosures | N/A | Not Ready | Called, Ethan Epling, phone number: (520) 730-0197. Drove to site no access and no activity. |
| 11/28/2025 | COT - HCEL - Electrical Underground | N/A | Re-inspection required | 11/28/25 LIGHT POLES: 1. West light pole is missing spare 3/4" stub out; Rebar clearance needs to be 3" minimum from earth, very little clearance on the sides. 2. South light pole caisson rebar sitting on the ground; Sonos tube installed upside down. 3. East light pole, 3" clearance needed on the sides for Rebar from earth and Sonos tube installed upside down. |
| 12/16/2025 | COT - HCEL - Outdoor Lighting | N/A | Partial Pass | 12/16/25 Needed Electrical underground for exterior lighting; Ok to backfill. |
| 12/18/2025 | COT - HCME - Mechanical Above Ceiling | N/A | Partial Pass | Partial pass for paddy, ok to wrap and insulate |
| 12/23/2025 | COT - HCBU - Building Progress | N/A | Partial Pass | 12/23/25: wire and lathe inspection |
| 01/09/2026 | COT - HCPL - Plumbing Progress | N/A | Partial Pass | Partial pass. Inspection is for wall approved for both DWV and domestic water lines. Isolators were mentioned for PVC running through metal studs. Possible leak at north end center of building above ceiling. Re pressurize system prior to next inspection. 1/9/2026 |
| 01/12/2026 | COT - HCPL - Plumbing Above Ceiling | N/A | Re-inspection required | 1/12/26: Per IPC table 308.5 horizontal supports on PVC is required 4’ o.c. (Supports over spaced throughout above ceiling and in wall), Per table 308.5 copper 1 1/4” or smaller required to have supports 6’ o.c at horizontal supports, properly secure copper piping throughout, R-3 insulation required at hot water piping 3/4” or larger, per previous notes |
| 01/06/2026 | COT - HCEL - Electrical Progress | N/A | Partial Pass | 1/6/26: electrical in-wall approved for rough-ins. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-COM-0525-00942
Permit Description: THE SCOPE OF WORK CONSISTS OF A NEW SINGLE TENANT GROUND UP PROJECT. THE STRUCTURE
INCLUDES, BUT IS NOT LIMITED TO, A REINFORCED STRUCTURAL CONCRETE SLAB, WOOD STUD
FRAMING & ENGINEERED WOOD JOISTS. INTERIOR CONSTRUCTION WILL COMPRISE OF METAL STUD
FRAMING. ALL NEW CONSTRUCTION WILL MATCH THAT ALLOWED PER THE CONSTRUCTION TYPE
LISTED BELOW.
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2025 | COT - HCPL - Sewer | Passed | ||
| 10/28/2025 | COT - HCBU - Excavation/Rebar/Zoning | Passed | Passed 10/28/25 ok to pour concrete | |
| 12/05/2025 | COT - HCBU - Roof Nailing | Passed | Passed 12/5/25 nailing per plans | |
| 12/05/2025 | COT - HCBU - Exterior Clips/Sheathing | Passed | Passed 12/5/25 nailing per plans | |
| 12/05/2025 | COT - HCBU - Framing | Passed | Passed 12/5/25 nailing per plans | |
| 01/14/2026 | BULD - Electrical Clearance | Passed | 1/14/26:ECO TEP CLEARANCE 10080 E OLD VAIL RD |