Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Above Ceiling

Permit Number - TC-COM-0525-00942

Inspection Description - COT - HCPL - Plumbing Above Ceiling

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/12/2026 COT - HCPL - Plumbing Above Ceiling Re-inspection required 1/12/26: Per IPC table 308.5 horizontal supports on PVC is required 4’ o.c. (Supports over spaced throughout above ceiling and in wall), Per table 308.5 copper 1 1/4” or smaller required to have supports 6’ o.c at horizontal supports, properly secure copper piping throughout, R-3 insulation required at hot water piping 3/4” or larger, per previous notes