Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Above Ceiling
Permit Number - TC-COM-0525-00942
Inspection Description - COT - HCPL - Plumbing Above Ceiling
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2026 | COT - HCPL - Plumbing Above Ceiling | Re-inspection required | 1/12/26: Per IPC table 308.5 horizontal supports on PVC is required 4’ o.c. (Supports over spaced throughout above ceiling and in wall), Per table 308.5 copper 1 1/4” or smaller required to have supports 6’ o.c at horizontal supports, properly secure copper piping throughout, R-3 insulation required at hot water piping 3/4” or larger, per previous notes |