Permit: TC-COM-0525-00942

Parcel: 141186590


Addresses:

10080 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Date Description Inspector Results Comments
10/16/2025 COT - HCEL - Electrical Underground  Partial Pass 10.16.25
Partial pending underground line to transformer. OK TO BACKFILL AND PROCEED WITH PROGRESS AREAS
11/13/2025 COT - HCEL - Electrical Underground  Partial Pass 11/13/25partial pass for trench, will check point of connection at later date. Ok to backfill
11/28/2025 COT - HCEL - Electrical Underground  Re-inspection required 11/28/25
LIGHT POLES:
1. West light pole is missing spare 3/4" stub out; Rebar clearance needs to be 3" minimum from earth, very little clearance on the sides.
2. South light pole caisson rebar sitting on the ground; Sonos tube installed upside down.
3. East light pole, 3" clearance needed on the sides for Rebar from earth and Sonos tube installed upside down.