Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2025 | COT - HCEL - Electrical Underground | Partial Pass | 10.16.25 Partial pending underground line to transformer. OK TO BACKFILL AND PROCEED WITH PROGRESS AREAS |
|
| 11/13/2025 | COT - HCEL - Electrical Underground | Partial Pass | 11/13/25partial pass for trench, will check point of connection at later date. Ok to backfill | |
| 11/28/2025 | COT - HCEL - Electrical Underground | Re-inspection required | 11/28/25 LIGHT POLES: 1. West light pole is missing spare 3/4" stub out; Rebar clearance needs to be 3" minimum from earth, very little clearance on the sides. 2. South light pole caisson rebar sitting on the ground; Sonos tube installed upside down. 3. East light pole, 3" clearance needed on the sides for Rebar from earth and Sonos tube installed upside down. |