Permit: TC-COM-0525-00942

Parcel: 141186590


Addresses:

10080 E OLD VAIL RD

Inspection Status: Not Ready

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
03/04/2026 COT - HCBU - Building Final  Not Ready
04/10/2026 COT - HCBU - Building Final  Re-inspection required 4-10-26: add a plastic bushing at the rooftop mini split disconnect, add a 90degree elbow at mop sink together with a hose, add a metallic label at rooftop's disconnect-the label must identify the purpose and the circuit.
04/29/2026 COT - HCBU - Building Final  Partial Pass 4-29-26: pending 3rd party outdoor lighting inspection.
05/01/2026 COT - HCBU - Building Final  Passed 5-1-26: Building final approved. Okay to apply for C of O.