Permit Reviews

Permit Number - TC-COM-0325-00541
Permit Status: Complete
Permit Description: Tenant improvement to an exiting shell building
Start Date Submittal Complete Date Status  
05/20/2025 COMMERCIAL REVIEW - FULL v.3 05/20/2025 APPROVED Review Details
04/23/2025 COMMERCIAL REVIEW - FULL v.2 05/13/2025 REQUIRES RESUBMIT Review Details
03/20/2025 COMMERCIAL REVIEW - FULL v.1 04/16/2025 REQUIRES RESUBMIT Review Details
09/02/2025 COMMERCIAL REVIEW - FULL REVISION v.1 09/29/2025 APPROVED Review Details
12/01/2025 COMMERCIAL REVIEW - FULL REVISION v.1 12/23/2025 APPROVED Review Details
10/29/2025 COMMERCIAL REVIEW - FULL REVISION v.1 11/18/2025 APPROVED Review Details
01/14/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 01/21/2026 APPROVED Review Details
05/20/2025 RESTAMP - COMMERCIAL v.1 05/28/2025 APPROVED Review Details

Conditions

Permit Number - TC-COM-0325-00541
Permit Status: Complete
Permit Description: Tenant improvement to an exiting shell building
Date Description Comments
03/20/2025 UNIT IDENTIFICATION
03/20/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
03/20/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
05/20/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
05/20/2025 SPECIAL INSPECTION FOR WELDING IS REQUIRED.

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-COM-0325-00541
Permite Description: Tenant improvement to an exiting shell building
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
11/25/2025 COT - HCBU - Building Progress N/A Partial Pass 11/25/2025 Frame/Screw Inspection. New vestibule area. All walls approved. Okay to tape and mud.
09/15/2025 COT - HCPL - Plumbing Progress N/A Re-inspection required 9-15-25: arrived on site at approximately 950am and noted that pour back had already occurred. Therefore, provide a letter to the city for review & approval documenting that pour back at plumbing areas was done per the 2018 IBC and per approved plans. The Letter must be submitted & approved prior to releasing a C of O.
01/15/2026 COT - HCBU - Building Final N/A Re-inspection required 1-15-26: lower unisex restroom mirror to 40" to the reflective surface, adjust restroom door to 5 pounds, label receptacle at south wall of business side, install bollard to protect water heater-have architect submit a letter to with installation details, water chlorination in progress-unable to check water, install drinking fountain faceplate, seal all penetrations above ceiling at warehouse side, install locking mechanism at restroom door, provide pictures of labeling of junction boxes at warehouse side, and paint exterior roof drain plastic.
01/15/2026 COT - HCME - Mechanical Final N/A Re-inspection required 1-15-26: lower unisex restroom mirror to 40" to the reflective surface, adjust restroom door to 5 pounds, label receptacle at south wall of business side, install bollard to protect water heater-have architect submit a letter to with installation details, water chlorination in progress-unable to check water, install drinking fountain faceplate, seal all penetrations above ceiling at warehouse side, install locking mechanism at restroom door, provide pictures of labeling of junction boxes at warehouse side, and paint exterior roof drain plastic.
01/15/2026 COT - HCPL - Plumbing Final N/A Re-inspection required 1-15-26: lower unisex restroom mirror to 40" to the reflective surface, adjust restroom door to 5 pounds, label receptacle at south wall of business side, install bollard to protect water heater-have architect submit a letter to with installation details, water chlorination in progress-unable to check water, install drinking fountain faceplate, seal all penetrations above ceiling at warehouse side, install locking mechanism at restroom door, provide pictures of labeling of junction boxes at warehouse side, and paint exterior roof drain plastic.
01/21/2026 COT - BULD - SWG Clearance N/A Not Applicable

Completed Inspections

Permit Status: Complete
Permit Number: TC-COM-0325-00541
Permit Description: Tenant improvement to an exiting shell building
Total Completed Inspections - 18
Date Description Inspector Results Comments
10/30/2025 COT - HCEL - Electrical Intermediate Passed Electric in wall per plan, ok to proceed to drywall
10/30/2025 COT - HCME - Mechanical Intermediate Passed Electric in wall per plan, ok to proceed to drywall
10/30/2025 COT - HCPL - Plumbing Intermediate Passed Plumbing in wall per plan, ok to proceed to drywall
12/04/2025 COT - HCEL - Electrical Above Ceiling Passed 12-4-25: electrical above ceiling approved.
12/04/2025 COT - HCBU - Building Progress Passed 12-4-25: framing for demising wall between suite 140-110 approved. Suite 170-drywall nailing for demising wall at upper portion to decking approved-okay for tape & texture.
12/04/2025 COT - HCME - Mechanical Progress Passed 12-4-25: approved.
12/04/2025 COT - HCEL - Electrical Progress Passed 12-4-25: approved.
01/05/2026 BULD - Electrical Clearance Passed 1-5-26: okay to energize Unit 150-2. ECO clearance issued to TEP.
01/14/2026 COT - FCON - Alarm - Final Passed
01/14/2026 COT - FCON - Fire - Final Passed
01/14/2026 ENGR Engineering Final Passed unit 150 exterior is complete and safe
01/14/2026 TRSP - ROW - Final/Close-Out Passed
01/14/2026 COT - FCON - Sprinkler - Final Passed Approved on 1/5/26 on permit TF-FCP-0925-00713
01/15/2026 COT - HCEL - Electrical Final Passed 1-15-26: approved.
01/14/2026 COT - HCPL - Plumbing Progress Passed 1-14-26: approved.
01/20/2026 COT - HCBU - Building Final Passed 1-20-26: building final approved.
01/20/2026 COT - HCME - Mechanical Final Passed 1-20-26: mechanical final approved.
01/20/2026 COT - HCPL - Plumbing Final Passed 1-20-26: plumbing final approved.

Documents

File Name Document Type  
COFO_FINALCOFO_COMMERCIAL (SSRS).PDF DOCUMENTS VIEW
LOFC_LETTEROFCOMPLETION (SSRS).PDF DOCUMENTS VIEW
COFO_TEMPORARYCOFO (SSRS).PDF DOCUMENTS VIEW
SUITE 150 TEST - BALANCE_V1.PDF DOCUMENTS VIEW
TORQUE REPORT SUITES 110, 140, 150, 160, 170 - 190_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
CONS-CORONA SPEC TI PERMIT REVISION 3 11-24-25_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-CORONA TI SPEC SUITE 150 REVISIONS 10-29-25_V1.PDF DOCUMENTS VIEW
NARRATIVE OF CHANGES 10-28-2025_V1.PDF DOCUMENTS VIEW
NARRATIVE OF CHANGES ELECTRICAL_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-2025-09-02 CORONA TI SUITE 150_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-CORONA TI SET RESUBMITTAL SUITE 150 4-21-25_V2.PDF DOCUMENTS VIEW
STRUCTURAL CALCULATIONS_SEALED 4-21-25_V2.PDF DOCUMENTS VIEW
SUITE 150 COMCHECK 04-22-2025_V2.PDF DOCUMENTS VIEW