Permit: TC-COM-0126-00127
Permit Details
Status:
Needs Resubmittal
Type:
Commercial Building
Address:
2800 E 36TH ST
Address NEW:
2800 E 36TH ST
Apply Date:
01/29/2026
Applicant:
David Williamson
Description:
New ground up classroom, common area, offices, storage, minor food service metal building structure with common material infill detached building addition to Rising Star Church
Permit Reviews
Permit Number - TC-COM-0126-00127
Permit Status: Needs resubmittal
Permit Description: New ground up classroom, common area, offices, storage, minor food service metal building structure with common material infill detached building addition to Rising Star Church
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/02/2026 | COMMERCIAL REVIEW - FULL v.1 | 02/24/2026 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0126-00127
Permit Status: Needs resubmittal
Permit Description: New ground up classroom, common area, offices, storage, minor food service metal building structure with common material infill detached building addition to Rising Star Church
Total Outstanding Activity Conditions - 22
| Date | Name |
|---|---|
| 02/02/2026 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |
| 02/02/2026 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
| 02/05/2026 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
| 02/05/2026 | An Outdoor Lighting Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
| 02/18/2026 | AIR BALANCING REPORT IS REQUIRED. |
| 02/18/2026 | Separate submittal to PC Industrial Wastewater Control is required for new interceptors and separators. Contact Kelsey.McMonagle@pima.gov or Adam.DeLaTorre@pima.gov for review and assessment of the proposed grease interceptor. |
| 02/18/2026 | WATER STERILIZATION REPORT IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. |
| 02/20/2026 | COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 02/20/2026 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED. |
| 02/20/2026 | Please submit a separate sign permit for an signs associated with this projet. |
| 02/20/2026 | SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED. |
| 02/20/2026 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
| 02/20/2026 | SPECIAL INSPECTION FOR SPECIAL MOMENT RESISTING STEEL FRAMES IS REQUIRED. |
| 02/20/2026 | Submit PREFABRICATED METAL BUILDINGS drawings and structural calculations. |
| 02/20/2026 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
| 02/20/2026 | SPECIAL INSPECTION FOR WELD REINF STEEL IS REQUIRED. |
| 02/20/2026 | SPECIAL INSPECTION FOR WELDING IS REQUIRED. |