Permit: T98CM02096
Permit Details
Status:
Revoked
Type:
SINGLE FAMILY NEW
Address:
441 W DAKOTA ST #01
Address NEW:
441 W DAKOTA ST #01
Apply Date:
05/13/1998
Applicant:
KONARSKI FRANK J & GABRIELA JT/R
Description:
FOURPLEX
Architects:
- KELLEY, ANDREW SCOTT
Contractors:
- F G P J DEVELOPMENT ,
Permit Reviews
Permit Number - T98CM02096
Permit Status: Revoked
Permit Description: FOURPLEX
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/10/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 03/28/2008 | COMPLETED |
| 03/28/2008 | 3RD PARTY REVIEW-COMMERCIAL | 04/03/2008 | COMPLETED |
| 04/03/2008 | REVISION - - 1ST | 05/27/2008 | COMPLETED |
| 05/27/2008 | REVISION - - 1ST | 09/16/2008 | COMPLETED |
| 09/16/2008 | REVISION - SITE | 09/18/2008 | COMPLETED |
| 10/24/2000 | REVISION | 02/14/2001 | COMPLETED |
Outstanding Inspections
Permit Status: Revoked
Permit Number: T98CM02096
Permite Description: FOURPLEX
Total Outstanding Inspections - 25
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| STEM WALL/RETAINING WALL | N/A | Not Inspected | ||
| BUILDING PRE-SLAB | N/A | Not Inspected | ||
| REINFORCED MASONRY PRE-GROUT | N/A | Not Inspected | ||
| U VALUE FOR WINDOW | N/A | Not Inspected | ||
| SHEET ROCK NAILING | N/A | Not Inspected | ||
| BUILDING - FINAL | N/A | Not Inspected | ||
| ELECTRIC - UFER | N/A | Not Inspected | ||
| PLUMBING - GAS PRESSURE TEST | N/A | Not Inspected | ||
| PLUMBING - FINAL | N/A | Not Inspected | ||
| MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| FIRE - FINAL | N/A | Not Inspected | ||
| LANDSCAPE - FINAL | N/A | Not Inspected | ||
| PERMIT FINALED | N/A | Not Inspected | ||
| 01/24/2008 | ROOF NAILING | N/A | Partial Approval | IVRS - Inspection :* 1. PLANS MUST BE REVISED FOR C.O.T APPROVAL TO MATCH AS BUILT 2. TRUSS DRAWINGS MUST BE APPROVED 3. OK TO DRY IN ROOF AT YOUR OWN RISK - SHEATHING IS OK REVISED PLANS REQUIRED |
| 01/24/2008 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* INSTALL BONDING RING ON RISER |
| 03/10/2005 | ENGINEERING - FINAL | N/A | Denied | SITE NOT READY AT THIS TIME. COMPLETE ALL WORK FOR THE STRUCTURE PRIOR TO CALLING FOR A RE-INSPECTION FOR THIS SITE. |
| 03/10/2008 | ELECTRIC - FINAL | N/A | Not ready for Inspection | |
| 03/10/2008 | PLUMBING - INTERMEDIATE | N/A | Partial Approval | UNDERGROUND FOR REVISION 1 PLUMBING OK TO COVER (BATHROOMS) |
| 03/20/2008 | STUCCO MESH | N/A | Partial Approval | IVRS - Inspection :* |
| 05/10/2000 | EXCAVATION/LAYOUT REBAR & ZON | N/A | Correction Required | ADDTL COMMS - 1. PROVIDE MIN 3 1/2 CONCRET ON TO 4 SLAB |
| 09/17/2004 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* OK ?, CABLE, POWER TO BEYOND SIDE WALK SOUTH END OF BLD |
| 11/28/2001 | BUILDING - PROGRESS | N/A | Denied | PROVIDE APPROVED PLANS FROM CITY OF TUCSON FOR PERIMETER WALL. YOU NEED A PERMIT FOR 6' WALL. CALLED FOR PROGRESS INSPECTION ON 4-PLEX HAD FOOTING FOR WALL READY, BUT WALL IS NOT PART OF THIS PERMIT. ADDITIONAL PERMIT REQUIRED FOR WALL.PERMIT SHOULDNT HAVE EXPIRED.THERE HAVE BEEN NO INSPECTION ON THIS PERMIT SINCE MAY OF 2000 THERE HAS BEEN NO PROGRESS HAS BEEN MADE ON4-PLEX FOR OVER 1 YEAR! EXPIRED PERMIT PER STEVE LONG. |
| 12/14/2007 | ELECTRIC - TEMP POWER FOR TEST | N/A | Not ready for Inspection | 1) YOU NEED #4 GROUNDING ELECTRODE CONDUCTOR CONNECTED TO 2 EACH GROUND RODS. 2) GROUNDING RODS NEED TO BE 6' APART. 3) YOU NEED TO HAVE YOUR TEMP MOUNTING PANEL SECURE. IT MAY NOT ROCK, TWIST, ETC. 4) YOU NEED TO CONNECT YOU METER SOCKET TO THE DISCONNECT PANEL. TEP DOES NOT SUPPLY THE METER SOCKET...ONLY THE WIRE FROM THE METER TO THE POLE. |
| 12/21/2007 | FRAMING | N/A | Not ready for Inspection | IVRS - Inspection :* 1) RECALL WHEN PLUMBING AND ELECTRIC IN |
Completed Inspections
Permit Status: Revoked
Permit Number: T98CM02096
Permit Description: FOURPLEX
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2000 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | ADDTL COMMS - 1. SOIL WATER TEST OK |
| 05/17/2000 | PLUMBING - SEWER HCS CONNECT | JSTANLEY | Approved | ADDTL COMMS - TEST ON SITE SEWER FROM EXISTING HCS TO BLDG TEST OK. OK TO BACKFILL |
| 05/22/2000 | PLUMBING - YARD WTR LINE/TEST | JSTANLEY | Approved | ADDTL COMMS - TEST ON SITE WATER OK REVISED PLAN ON FILE OK TO BACKFILL |
| 12/21/2007 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection :* 1) INSTALL LT ANCHORS AT 8 LOCATIONS (6 BACK AND 2 FRONT) TO CORRECT SHEAR PANELS 2) YOU CAN USE LTT131 ? LTT 19 WITH 3/4" EPOXIED ANCHOR BOLT OR AN HTT 3) OK TO LATH |
| 03/10/2008 | ELECTRIC - TEMPORARY SERVICE | LHANLY | Approved | |
| 03/10/2008 | ELECTRIC - CABLE DROP | LHANLY | Approved | |
| 03/11/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR "4-PLEX" PER L. HANLY |