Permit: T98CM02096

Parcel: 137060500


Addresses:

441 W DAKOTA ST #01

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
12/14/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection 1) YOU NEED #4 GROUNDING ELECTRODE CONDUCTOR CONNECTED TO 2 EACH GROUND RODS.

2) GROUNDING RODS NEED TO BE 6' APART.

3) YOU NEED TO HAVE YOUR TEMP MOUNTING PANEL SECURE. IT MAY NOT ROCK, TWIST, ETC.

4) YOU NEED TO CONNECT YOU METER SOCKET TO THE DISCONNECT PANEL. TEP DOES NOT SUPPLY THE METER SOCKET...ONLY THE WIRE FROM THE METER TO THE POLE.
12/11/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection BUILD TEMP SERVICE PRIOR TO CALLING INSPECTION, MUST BE COMPLETE WITH GROUNDS AND ALL CONNECTIONS.