Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T19CM02046
Permit Details
Apply Date:
03/22/2019
Applicant:
N/A
Description:
PV SHADE CANOPIES
Contractors:
- SOLON CORPORATION ***APA***
- PARK N SHADE OF TUCSON INC
Permit Reviews
Permit Number - T19CM02046
Permit Status: L of c
Permit Description: PV SHADE CANOPIES
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/22/2019 | PLANS OK TO SUBMIT - COMM | 03/22/2019 | COMPLETED |
03/22/2019 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 05/06/2019 | COMPLETED |
05/06/2019 | RESUBMITTAL | 05/09/2019 | COMPLETED |
Completed Inspections
Permit Status: L of c
Permit Number: T19CM02046
Permit Description: PV SHADE CANOPIES
Total Completed Inspections - 13
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2019 | EXCAVATION/LAYOUT REBAR & ZON | DMUNIZ | Approved | Phase 2 of project. Columns E,F,G,H are Ok to pour footings |
06/20/2019 | ELECTRIC - UNDERGROUND | DMUNIZ | Approved | Phase 1 to Phase 2 of Project, Completion of Electrical Underground Conduits Approved and ok to tape encase and backfill. |
06/30/2019 | ELECTRIC - PROGRESS | DMUNIZ | Approved | Cleared (RECN). Transformer is customer owned no TEP Clearance is required at this time, record for PDSD. Inspection called for Line side tap in Existing Transformer, from New 800AMP PV Utility Disconnect. (DGL) to be issued at Final Inspection. 3 Parallel sets of 480V #500 KCMIL Conductors, 1/0 GRND. Lugs torqued at 32 PSI. All work meets NFPA70 (2017 NEC), and local jurisdiction Requirements. Note: Check for $165 collected upon arrival for after hours inspection. |
06/30/2019 | ELECTRIC - OUTDOOR LIGHTING | DMUNIZ | Approved | |
06/30/2019 | ELECTRIC - INTERMEDIATE | DMUNIZ | Approved | |
06/30/2019 | FRAMING | DMUNIZ | Approved | |
06/30/2019 | ELECTRIC - UFER | DMUNIZ | Approved | |
07/09/2019 | FIRE - FINAL | JPEELDAVIS | Approved | |
07/09/2019 | BUILDING - FINAL | DMUNIZ | Approved | Pending fire final. |
07/09/2019 | TEP CLEARANCE - PM | DMUNIZ | Approved | CODE DGC |
07/09/2019 | OUTDOOR LIGHTING FINAL | DMUNIZ | Approved | |
07/09/2019 | ELECTRIC - FINAL | DMUNIZ | Approved | Clear TEP (DGC). |
07/09/2019 | ENGINEERING - FINAL | RLEDONNE | Approved |