Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T19CM02046
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2019 | ELECTRIC - UFER | Approved | ||
06/13/2019 | ELECTRIC - UFER | Not ready for Inspection | Called in wrong inspection, needed 2010 | |
06/12/2019 | ELECTRIC - UFER | Partial Approval | (EGC) for Grid lines E,F,G,H. Located on North ends of columns 25’ coiled in footers, to be bonded to PV system at later date. | |
05/15/2019 | ELECTRIC - UFER | Partial Approval | (EGC) for Grid A,B,C,D ok. 20’ #4 Bare copper coiled in footers on North end of columns, to be bonded to system. |