Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T16CM06538
Permit Details
Apply Date:
08/23/2016
Applicant:
SCARANO, VINCENT (DEREK WILSON)
Description:
MULTI FAMILY UNIT
Architects:
- SCARANO, VINCENT
Contractors:
- KITCHELL CONTRACTORS INC OF ARIZ
Permit Reviews
Permit Number - T16CM06538
Permit Status: C of o
Permit Description: MULTI FAMILY UNIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/21/2018 | REVISION - - 1ST | 08/20/2018 | COMPLETED |
| 05/26/2017 | REVISION - - 1ST | 12/28/2017 | COMPLETED |
| 08/11/2017 | REVISION - - 1ST | 12/28/2017 | COMPLETED |
| 08/20/2018 | REVISION - - 2ND | 12/13/2018 | COMPLETED |
| 08/23/2016 | PLANS OK TO SUBMIT - COMM | 12/28/2017 | COMPLETED |
| 08/23/2016 | COMMERCIAL - TI | 12/28/2017 | COMPLETED |
| 10/07/2016 | RESUBMITTAL - TI ALL | 12/28/2017 | COMPLETED |
| 11/08/2016 | RESUBMITTAL - TI ALL | 12/28/2016 | COMPLETED |
| 12/13/2018 | REVISION - - 2ND | 12/18/2018 | ACTIVE |
| 12/20/2017 | REVISION - - 1ST | 02/21/2018 | COMPLETED |
| 12/28/2016 | REVISION - - 1ST | 12/28/2017 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T16CM06538
Permit Status: C of o
Permit Description: MULTI FAMILY UNIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/23/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T16CM06538
Permit Description: MULTI FAMILY UNIT
Total Completed Inspections - 39
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2017 | ELECTRIC - UFER | BSTEVENS | Approved | UFER IS IN PLACE ON WEST SIDE OF SLAB. |
| 07/21/2017 | STEM WALL/RETAINING WALL | BSTEVENS | Approved | |
| 07/21/2017 | REINFORCED MASONRY PRE-GROUT | BSTEVENS | Approved | |
| 09/01/2017 | ROOF NAILING | BSTEVENS | Approved | |
| 09/01/2017 | EXT METAL CLIPS/EXT SHEATHING | BSTEVENS | Approved | |
| 10/06/2017 | SHEET ROCK NAILING | JBURGE | Approved | BUILDING "A", LEVEL #1, HALLWAYS, ROOMS. OK TO TAPE PROGRESS AREAS. |
| 10/27/2017 | STUCCO MESH | BSTEVENS | Approved | |
| 12/14/2017 | FIREWALL/FIREBARRIER/FIRESTOP | BSTEVENS | Approved | |
| 12/14/2017 | MECHANICAL - PROGRESS | BSTEVENS | Approved | |
| 12/14/2017 | MECHANICAL - ABOVE CEILING | BSTEVENS | Approved | |
| 12/14/2017 | MECHANICAL - INTERMEDIATE | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - PROGRESS | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - SEWER HCS CONNECT | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - YARD WTR LINE/TEST | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - ABOVE CEILING | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - INTERMEDIATE | BSTEVENS | Approved | |
| 12/14/2017 | PLUMBING - ROUGH, SOIL | BSTEVENS | Approved | |
| 12/14/2017 | ELECTRIC - PROGRESS | BSTEVENS | Approved | |
| 12/14/2017 | ELECTRIC - ABOVE CEILING | BSTEVENS | Approved | |
| 12/14/2017 | ELECTRIC - INTERMEDIATE | BSTEVENS | Approved | |
| 12/14/2017 | BUILDING - PROGRESS | BSTEVENS | Approved | |
| 12/14/2017 | BUILDING ABOVE CEILING | BSTEVENS | Approved | |
| 12/14/2017 | FRAMING | BSTEVENS | Approved | |
| 12/19/2017 | ELECTRIC - UNDERGROUND | BSTEVENS | Approved | PARKING LOT LIGHTS, SES, OK TO COVER CONDUITS |
| 12/19/2017 | ELECTRIC - TEMPORARY SERVICE | BSTEVENS | Approved | 3 PHASE TO MAIN HOUSE GEAR OK TO FEED. SES-1 BUILDING 1 OK TO POWER |
| 12/28/2017 | MECHANICAL - FINAL | BSTEVENS | Approved | UNIT 102 IS READY FOR OCCUPANCE AS A MODEL. ALL CONSTRUCTION ACTIVITY MUST BE PHYSICALLY SEPERATED FROM PUBLIC AREAS. I RECOMMEND APPROVAL OF TCO WITH LIMITATIONS. |
| 12/28/2017 | PLUMBING - FINAL | BSTEVENS | Approved | UNIT 102 IS READY FOR OCCUPANCE AS A MODEL. ALL CONSTRUCTION ACTIVITY MUST BE PHYSICALLY SEPERATED FROM PUBLIC AREAS. I RECOMMEND APPROVAL OF TCO WITH LIMITATIONS. |
| 12/28/2017 | FIRE - FINAL | GD'AURIA | Approved | OK FOR TCO FIRE WATCH REQUIRED PER GDA'URIA |
| 12/28/2017 | FIRE - ALARM FINAL | GD'AURIA | Approved | OK FOR TCO FIRE WATCH REQUIRED PER GDA'URIA |
| 12/28/2017 | FIRE SPKLR - FINAL | jvincent | Approved | see all notes under sprink permit. PA only on room #102 and the hallway/corridor that serves that room. This was only done so they could get TCO. Main drain test 51-42-50. Harvey to consult with Ryan fire protection due to low numbers. Still needs a full walk through after all heads trimmed out. 1) waiting on updated calcs after backflows were added. 2) need knox fdc plug 3) label riser room door, "riser room" 4) need fire bell installed. 5) min 2" drain needs to be installed due to backflows. currently 1 1/4" 6) still need full sprink final. |
| 12/29/2017 | ELECTRIC - CONSTRUCTION POWER | BSTEVENS | Approved | SES 2 - UNITS 104,204,304,305,106,206,306,205,107,207 SES 3 - UNITS 111,211,110,210,108,208,109,209,309,308 |
| 03/23/2018 | TEP CLEARANCE - AM | BSTEVENS | Approved | ECO |
| 06/08/2018 | U VALUE FOR WINDOW | BSTEVENS | Approved | |
| 12/27/2018 | ZONING - FINAL | CTREVI | Approved | |
| 12/28/2018 | OUTDOOR LIGHTING FINAL | CTREVIL | Approved | ADMINISTRATIVE APPROVAL |
| 12/28/2018 | ELECTRIC - FINAL | CTREVIL | Approved | ADMINISTRATIVE APPROVAL |
| 12/28/2018 | BUILDING - FINAL | CTREVIL | Approved | ADMINISTRATIVE APPROVAL |
| 12/28/2018 | BUILDING PRE-SLAB | CTREVIL | Approved | ADMINISTRATIVE APPROVAL |
| 12/28/2018 | EXCAVATION/LAYOUT REBAR & ZON | CTREVIL | Approved | ADMINISTRATIVE APPROVAL |