Review Details: REVISION - - 1ST

Permit Number - T16CM06538
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/18/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2017 CLAURIE1 DESIGN PROFESSIONAL REVIEW Reqs Change DATE: November 6, 2016, Revised December 9, 2016, Revised December 21, 2016
January 13, 2017
TO: IID Design Review Committee
c/o Carolyn Laurie, Principal Planner
Planning & Development Services
City of Tucson
201 N Stone Avenue
Tucson, AZ 85701
FROM: Corky Poster, Architect/Planner (AICP)
City of Tucson On-Call Design Professional
RE: IID-16-03
7th Avenue Commons
58 East 5th Street
Tucson, AZ 85705
OWNER: Gardner Capital Development, Reid Butler, President
ARCHITECT: Biltform Architecture
PHASE OF REVIEW:
Review of Permit Submittal
MATERIAL REVIEWED:
Submittal from applicant to the City of Tucson for building permit
IID STANDARDS APPLICABLE TO PROJECT:
Check for conformance with IID approval Conditions
SUMMARY OF CONDITIONS (See City of Tucson formal letter for precise conditions):
1. Stone Avenue usable retail space
2. 30 parking spaces
3. 5th Street and Stone Avenue elevations
4. Back-in spaces on east side of 7th Avenue
5. North Elevation Clubhouse refinements
6. Enhanced Building elevations
7. Refinement of outdoor areas
8. Staff and Design Professional review
FINDINGS:
A. North elevation of the Clubhouse on 5th Street on A5.6.1 is good. It corresponds to the
color elevations drawing on the most recent booklet submittal and address the
concerns of the Design Professional. It satisfies the conditions re: 5 above.
B. Re: 3 above, elevations shown on A6.3.0 are not sufficient.
· Metal canopies on Stone Avenue West Elevation are shown but not noted or
labeled or tied to a corresponding detail drawing.
· Landscape vines on North Elevation are not shown on A6.3.0, nor on the Landscape
Plan L1.1, nor supported by the Irrigation Plan on I1.1.
· Wire mesh on the North Elevation of A6.3.0 are shown but not noted or labeled or
tied to a corresponding detail drawing.
· Accentuated Building Entries re: 6 above are shown and labeled on the North
Elevation of A5.6.1., the South Elevation of A5.6.1, on the East Elevation of A5.6.2,
on the West Elevation of A5.6.3, but not on the North Elevation or West Elevation
of A6.3.0.
C. Re: 1 above, Usable space on Stone Avenue is satisfactorily resolved as shown on A1.0.
Please clarify the use of the language “Deferred Submittal” on the Hubbard Engineering
Sheets. Is the office space on Stone Avenue likely to change or is it to be built as
shown?
D. Refinements of outdoor space re: 7 above is satisfactory.
E. Re: 2 and 4 above, these conditions are being reviewed by others.
Submitted by:
Corky Poster, Architect/Planner, Poster Frost Mirto
City of Tucson Design Professional
12/28/2017 LOREN MAKUS ENGINEERING REVIEW Reqs Change Please provide a revised DP to match the changes to the site.
12/28/2017 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change APPROVAL PENDING DESIGN PROFESSIONAL. MODIFICATIONS TO ELEVATIONS WILL ALTER BUILDING REVIEW
12/28/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 7th Avenue Commons - Building Plan
T16CM06538
Building Plan (Revision)

TRANSMITTAL DATE: January 9, 2017

DUE DATE: January 24, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The vehicle parking calculation shown on sheet A1.0 does not match what is shown on sheet 5 of the approved development package. A revision to the development package will be required prior to approval of the building plan.

3. The twelve (12) Civil sheets provided in the building plans will either need to be marked as "FOR REFERENCE ONLY SEE DP16-0144" of provide the approved development package sheets in the building plan.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
05/26/2017 MMENDIB1 OUT TO CUSTOMER Completed