Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T15BU00706
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
6803 S PALO VERDE RD
Address NEW:
6803 S PALO VERDE RD
Apply Date:
06/22/2015
Applicant:
MARK BECK
Description:
SPRKL UNDERGORUND & HYDRANTS
Contractors:
- LAYTON CONSTRUCTION CO INC
Outstanding Activity Conditions
Permit Number - T15BU00706
Permit Status: Final
Permit Description: SPRKL UNDERGORUND & HYDRANTS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/22/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU00706
Permit Description: SPRKL UNDERGORUND & HYDRANTS
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2015 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | Completed All 10 inch and 12 inch lines tested at 200 PSI for 2 hours. |
| 12/15/2015 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | Flushed all hydrants and risers stubs with a burlap sack all showed clean, also flushed the FDC's. |
| 12/15/2015 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | Flushed all hydrants and risers stubs with a burlap sack all showed clean, also flushed the FDC's. |
| 12/22/2015 | FIRE - HYDRANTS | kenb | Approved | TUCSON WATER IS STATING THAT THEY NO LONGER HAVE THE FUNDING TO PROVIDE LOCKS ON THE PRIVATE HYDRANTS. THIS CONDITION HAS BEEN REMOVED |