Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
06/22/2015
Applicant:
MARK BECK
Description:
SPRKL UNDERGORUND & HYDRANTS
Contractors:
  • LAYTON CONSTRUCTION CO INC

Outstanding Activity Conditions

Permit Number - T15BU00706
Permit Status: Final
Permit Description: SPRKL UNDERGORUND & HYDRANTS
Total Outstanding Activity Conditions - 1
Date Name
06/22/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T15BU00706
Permit Description: SPRKL UNDERGORUND & HYDRANTS
Total Completed Inspections - 4
Date Description Inspector Results Comments
11/03/2015 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved Completed
All 10 inch and 12 inch lines tested at 200 PSI for 2 hours.
12/15/2015 FIRE SPKLR - FINAL CSCHULTZ Approved Flushed all hydrants and risers stubs with a burlap sack all showed clean, also flushed the FDC's.
12/15/2015 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved Flushed all hydrants and risers stubs with a burlap sack all showed clean, also flushed the FDC's.
12/22/2015 FIRE - HYDRANTS kenb Approved TUCSON WATER IS STATING THAT THEY NO LONGER HAVE THE FUNDING TO PROVIDE LOCKS ON THE PRIVATE HYDRANTS. THIS CONDITION HAS BEEN REMOVED