Inspection History: FIRE - HYDRANTS

Permit Number - T15BU00706

Inspection Description - FIRE - HYDRANTS

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2015 FIRE - HYDRANTS Approved TUCSON WATER IS STATING THAT THEY NO LONGER HAVE THE FUNDING TO PROVIDE LOCKS ON THE PRIVATE HYDRANTS. THIS CONDITION HAS BEEN REMOVED
12/15/2015 FIRE - HYDRANTS Partial Approval Flushed all hydrants and risers stubs with a burlap sack all showed clean, also flushed the FDC's.
ALL PRIVATE HYDRANTS WILL REQUIRE TO HAVE LOCKS INSTALLED BY TUCSON WATER'S CONTRACTOR AT NO COST TO OWNER
12/10/2015 FIRE - HYDRANTS Partial Approval Partial Approval
Flushed hydrants:
NE corner, All North side, all West side

Flushed 1 riser on NE most side.

Still need to complete South side and East side hydrant flushes and remaining stub ups ( x 9).