Permit: T11CM02877
Permit Details
Apply Date:
09/07/2011
Applicant:
KEN WEYKER
Description:
TI/REPLACE HVAC
Contractors:
- F M I HEATING AND COOLING
Permit Reviews
Permit Number - T11CM02877
Permit Status: Final
Permit Description: TI/REPLACE HVAC
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/06/2013 | REVISION - - 1ST | 09/12/2013 | COMPLETED |
09/07/2011 | PLANS OK TO SUBMIT - COMM | 09/07/2011 | COMPLETED |
09/07/2011 | COMMERCIAL - TI | 09/28/2011 | COMPLETED |
09/12/2013 | REVISION - - 1ST | 10/09/2013 | COMPLETED |
10/26/2011 | RESUBMITTAL | 11/30/2011 | COMPLETED |
11/30/2011 | OTHER | 04/23/2012 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T11CM02877
Permit Description: TI/REPLACE HVAC
Total Completed Inspections - 12
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2012 | MECHANICAL - FINAL | MRAMBER | Approved | 1. PROVIDE SCREW SPACING IN ROUND DUCT PER SMAC STANDARDS 2. PROVIDE DUCT SITFFENERS IN RECT DUCT PER SMACN STANDARDS BASED ON DUCT WIDTHS, GAGS, PRESS GLASSEXHAUST DUCTING 3. DAMAGED WIRING AT UNIT DISCONNECTS 4. UNITS OVER FUSED 5. EC-2.7,2.8-2.9 OK TO INSULATE EXTERIOR DUCT |
10/30/2012 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | 1. BLDG 2 WORD SHOP E.C 2.1 & 2.2 &2.4 OK TO INSULATE EXTERIOR DUCT 2. BLDG 2 WELD SHOP E.C 2.3 ADD STIFFENERS AS REQUIRED BY SMACNA 3. DUCT AT E.F 2.2 OK |
12/11/2012 | PLUMBING - FINAL | BBENEDON | Approved | PIPE CONDENSATE. TERMINATE B VENT 1' ABV ANY VERTICAL SURFACE W/IN 8'. 503.6.4 HGC. INSTALL A SOV IMMEDIATELY UP STRM AND DOWN STRM OF MP REG. 410.2 COMPLETE WORK |
12/11/2012 | PLUMBING - GAS PRESSURE TEST | BBENEDON | Approved | IVRS - Inspection :* |
05/20/2013 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* |
05/20/2013 | PLUMBING - GAS PRESS TEST FNL | JMILITEL | Approved | IVRS - Inspection :* |
05/20/2013 | FIRE - FINAL | CSCHULTZ | Approved | |
05/20/2013 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
05/24/2013 | ELECTRIC - FINAL | MRAMBER | Approved | IVRS - Inspection :* |
07/31/2013 | ELECTRIC - ABOVE CEILING | MRAMBER | Approved | |
07/31/2013 | ELECTRIC - INTERMEDIATE | MRAMBER | Approved | |
10/16/2013 | BUILDING - FINAL | LHANLY | Approved |