Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM02877
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2013 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/07/2013 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE SCREENS ON REGULATOR VENT OUTLETS |
|
03/06/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*SOAP TEST FINAL CONNECTIONS CORRECT SLOPE OF HORIZONTAL VENT PROTECT PVC FROM UV RAYS INSTALL MISSING CLAMPS PROVIDE CLEARANCE BETWEEN SEDIMENT TRAP AND GROUND SCREEN REGULATOR VENT TERMINATIONS TAPPED ELBOW IS A CODE VIOLATION |
|
02/07/2013 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY SOV DOWN STREAM OF M.P. REG. 2) PROVIDE PRESS TEST ON LOW PRESS GAS LINES. |
|
12/11/2012 | PLUMBING - FINAL | Not ready for Inspection | PIPE CONDENSATE. TERMINATE B VENT 1' ABV ANY VERTICAL SURFACE W/IN 8'. 503.6.4 HGC. INSTALL A SOV IMMEDIATELY UP STRM AND DOWN STRM OF MP REG. 410.2 COMPLETE WORK |