Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM02877
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/20/2013 | MECHANICAL - FINAL | Approved | AIR BALANCE REPORT OK | |
03/27/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
03/07/2013 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FLUE EXHAUST ON TUVE HEATERS NOT PROPERLY INSTALLED, PROVIDE MANUFACTURERS INSTALLATION INSTRUCTION AT NEXT INSPECTION. |
|
02/07/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEM DATED 8-31-12 OK 2) PROVIDE AIR BALANCE REPORT |
|
08/31/2012 | MECHANICAL - FINAL | Not ready for Inspection | 1. PROVIDE SCREW SPACING IN ROUND DUCT PER SMAC STANDARDS 2. PROVIDE DUCT SITFFENERS IN RECT DUCT PER SMACN STANDARDS BASED ON DUCT WIDTHS, GAGS, PRESS GLASSEXHAUST DUCTING 3. DAMAGED WIRING AT UNIT DISCONNECTS 4. UNITS OVER FUSED 5. EC-2.7,2.8-2.9 OK TO INSULATE EXTERIOR DUCT |