Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Apply Date:
06/02/2011
Applicant:
WATSON, JAMES RICHARD
Description:
TI: MECHANICAL BUILDING - S.W. GAS CORP
Architects:
  • WATSON, JAMES RICHARD
Contractors:
  • MIDSTATE MECHANICAL INC ,

Permit Reviews

Permit Number - T11CM01705
Permit Status: Final
Permit Description: TI: MECHANICAL BUILDING - S.W. GAS CORP
Start Date Submittal Complete Date Status  
06/02/2011 PLANS OK TO SUBMIT - COMM 06/02/2011 COMPLETED Review Details
06/02/2011 COMMERCIAL - TI 07/12/2011 COMPLETED Review Details
07/12/2011 RESUBMITTAL 08/01/2011 COMPLETED Review Details
08/01/2011 RESUBMITTAL 08/23/2011 COMPLETED Review Details
08/23/2011 RESUBMITTAL 08/25/2011 COMPLETED Review Details
08/25/2011 RESUBMITTAL 08/25/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11CM01705
Permit Status: Final
Permit Description: TI: MECHANICAL BUILDING - S.W. GAS CORP
Total Outstanding Activity Conditions - 1
Date Name
06/02/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T11CM01705
Permit Description: TI: MECHANICAL BUILDING - S.W. GAS CORP
Total Completed Inspections - 31
Date Description Inspector Results Comments
10/07/2011 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
1) OK 1 1/2" 1" 3/4" FOR PUMPS MECH YARD
2) BE ADVISED, EXPOSED PVC TO BE SCHEDULE 80 PER CITY OF TUCSON AMENDMENTS
10/11/2011 EXCAVATION/LAYOUT REBAR & ZON MHENSON Approved IVRS - Inspection :*
1) COOLING TOWER-2 FOOTINGS
10/11/2011 BUILDING - FINAL MHENSON Approved IVRS - Inspection :*
1) NEED SPECIAL INSPECTION CERT SIGNED BY BLDG OFFICIAL
10/18/2011 MECHANICAL - UNDERGROUND MRAMBER Approved IVRS - Inspection :*
10/31/2011 PLUMBING - PRE SLAB RRICH Approved IVRS - Inspection :*
1) GHP YARD ENCLOSURE OK FOR CLEANOUTS
10/31/2011 SITE - SEWER RRICH Approved IVRS - Inspection :*
10/31/2011 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*
11/03/2011 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
1) NEED 30" HORIZONTAL 36" IN FRONT OF DISCONNECT
11/04/2011 SHEET ROCK NAILING MHENSON Approved IVRS - Inspection :*
1) NO SHEETROCK
11/10/2011 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
1) ALL NEW VAV AT BLDG B OK TO COVER
11/10/2011 MECHANICAL - HYDRONIC PIPING MRAMBER Approved IVRS - Inspection :*
11/10/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
02/23/2012 FRAMING JBURGE Approved IVRS - Inspection :*
03/15/2012 ELECTRIC - ABOVE CEILING RMORENO Approved IVRS - Inspection :*
03/15/2012 ELECTRIC - UFER RMORENO Approved IVRS - Inspection :*
03/23/2012 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
03/29/2012 FIRE - FINAL CSCHULTZ Approved Install signs Per IFC 912.2.2
03/29/2012 FIRE SPKLR - FINAL CSCHULTZ Approved
04/05/2012 NPPO - FINAL MRUSSO Approved
04/05/2012 LANDSCAPE - FINAL MRUSSO Approved
04/27/2012 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
04/27/2012 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
04/27/2012 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
05/16/2012 OUTDOOR LIGHTING FINAL DSANTACR Approved IVRS - Inspection :*
05/24/2012 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
1) COMPLETE PIPE INSULTION IN MECH ROOM
2) PROVIDE SCREEN AT BOTTOM OF MECH. ROOM EXHAUST
3) PROVIDE AIR BALANCE REPORT
4) PROVIDE SMOKE FOR DUCT SMOKE DETECTOR TESTING, MECH, CONTRACTOR TO BE ON SITE FOR TEST
5) REMOVE THREADS FROM CONDENSATE VENTS
6) PROVIDE APPROVED DUCT STIFFNERS (SEE SMACNA STANDARDS)
05/29/2012 RIGHT OF WAY - FINAL MCASTRO Approved
08/07/2012 ELECTRIC - PROGRESS MRAMBER Approved
08/07/2012 ELECTRIC - OUTDOOR LIGHTING MRAMBER Approved
08/07/2012 ELECTRIC - FINAL MRAMBER Approved IVRS - Inspection :*
03/20/2013 SIGN - FINAL MRUSSO Approved
03/21/2013 ENGINEERING - FINAL RLEDONNE Approved PER MIKE

Documents

File Name Document Type  
None DOCUMENTS VIEW