Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) EF 1 AND 3 AND RF-4 NOT MEETING MINIMUM REQUIREMENTS 2) NEED TO ADDRESS CORRECTIONS DATED 5-24-12 |
|
| 05/24/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE PIPE INSULTION IN MECH ROOM 2) PROVIDE SCREEN AT BOTTOM OF MECH. ROOM EXHAUST 3) PROVIDE AIR BALANCE REPORT 4) PROVIDE SMOKE FOR DUCT SMOKE DETECTOR TESTING, MECH, CONTRACTOR TO BE ON SITE FOR TEST 5) REMOVE THREADS FROM CONDENSATE VENTS 6) PROVIDE APPROVED DUCT STIFFNERS (SEE SMACNA STANDARDS) |