Permit Number: T11CM01705
Parcel: 13220003A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01705
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Provide structural calculations for the new cooling tower base support (detail 113/M2.0) and clarify the installation of the support. Provide dimensions for the proposed bases, the number of bases to be used, and the bearing surface for the foot pads. Reference: Sections 106.3.1, IMC 2006.
08/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved