Permit: T11CM01705

Parcel: 13220003A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM01705

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/21/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) HAVE ENGINEER OF RECORD CLARIFY SUMP MP CONNECTION, PLUG CONNECTED TO GFI RECEPT IDE PIT MAY PRESENT TRIPPING PROBLEM, SL, SW, DOOR MUST OPEN 90 DEGREE PER 110 NEC BACK PUMP #7
2) STRAP ALL CONDUITS TO CODE, INCLUDING CONTROL CONDUITS PER NEC
3) BOND X-FORMER TO BLDG STEEL IN CONTROL ROOM
4) BOND CONNECTOR IN SUPPLY FAN DISC. SW. BLDG #B
05/17/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE HAVE CONTRACTOR ON SITE TO OPEN EQUIPMENT AS NECESSARY FOR INSPECTION