Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM01705
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/21/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) HAVE ENGINEER OF RECORD CLARIFY SUMP MP CONNECTION, PLUG CONNECTED TO GFI RECEPT IDE PIT MAY PRESENT TRIPPING PROBLEM, SL, SW, DOOR MUST OPEN 90 DEGREE PER 110 NEC BACK PUMP #7 2) STRAP ALL CONDUITS TO CODE, INCLUDING CONTROL CONDUITS PER NEC 3) BOND X-FORMER TO BLDG STEEL IN CONTROL ROOM 4) BOND CONNECTOR IN SUPPLY FAN DISC. SW. BLDG #B |
|
05/17/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE HAVE CONTRACTOR ON SITE TO OPEN EQUIPMENT AS NECESSARY FOR INSPECTION |