Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
05/31/2011
Applicant:
GASTON MARCHANO
Description:
TI: MICRO BREWERY
Architects:
  • CATALANO, VINCENT VICTOR
Contractors:
  • BAIRD BUILDERS INC ,

Permit Reviews

Permit Number - T11CM01643
Permit Status: C of o
Permit Description: TI: MICRO BREWERY
Start Date Submittal Complete Date Status  
02/21/2012 REVISION - - 2ND 02/21/2012 COMPLETED Review Details
05/31/2011 COMMERCIAL - TI 06/08/2011 COMPLETED Review Details
06/08/2011 RESUBMITTAL 06/09/2011 COMPLETED Review Details
09/22/2011 REVISION - - 1ST 09/22/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11CM01643
Permit Status: C of o
Permit Description: TI: MICRO BREWERY
Total Outstanding Activity Conditions - 2
Date Name
05/31/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
06/09/2011 June 8, 2011 (No special Inspection Required). FLOODPLAIN USE PERMIT NO. T11OT01148 ADDRESS: 1859 W. Grant Rd. St. #111, Tucson, Arizona, 85745 PROPERTY OWNER'S NAME: Rod Walker - Walker Tucson Properties The applicant is authorized to use a portion of the flood hazard area in the City of Tucson on the property described as (legal description): A portion of the South 286.87' of the North 650.55' in the Northeast quarter of the Northwest quarter lying westerly and adjacent to the drainageway. Being 4.57 AC. as recorded in Book 3 of Maps and Plats at Page 15, all in Section 03, T-14-S, R-13-E, in the recorders office of Pima County, Arizona, for the purpose of constructing improvements to an existing commercial/residential building. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit. The following conditions shall apply to this permit. (Or refer to Chapter 26 page 35) 1. All work shall conform to the attached plans (Drainage Report and all improvement plans) which are made part of this permit. 2. The construction cost of the improvements shall not exceed 50% of the total appraised/assessed value of the existing structure, not including the land. Estimated cost of improvement (construction) = $132,292.00 Assessed value (2011) of the existing improvements (i.e. structure), excluding the value of the land = $1,400,792.0 The percentage of improvements to the existing residence: $132,292.00/ $1,400,792.0= 0.0944 (100) = 1.0% 3. The existing drainage patterns at the property lines shall not be obstructed or changed. 4. Within 5 (five) days of issuance of this permit, through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "Construction proceeding under requirements of City of Tucson Floodplain Use Permit No. T11OT00000. For information please call 791-5550." 5. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 6. This permit becomes invalid and is subject to additional floodplain review, if any required development permit (s') changes the configuration of the structure and or site development. 7. Any patio walls to be constructed will require a separate Floodplain Use Permit. This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions set forth in this permit are not complied with. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Section. (EXPIRATION DATE) Month: 06 Day: 09 Year: 2012 APPLICANT NAME: Dragoon Brewing Company, LLC ADDRESS: 1859 W. Grant Rd., #111 CITY: Tucson, Arizona, 85745 PHONE NO.: (520) 329-3606 ___________________________ _____________ APPLICANT'S SIGNATURE: DATE: The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Completed Inspections

Permit Status: C of o
Permit Number: T11CM01643
Permit Description: TI: MICRO BREWERY
Total Completed Inspections - 30
Date Description Inspector Results Comments
09/29/2011 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
11/01/2011 PLUMBING - PRE SLAB RMYERS Approved IVRS - Inspection :*
11/08/2011 FRAMING GDABBS Approved IVRS - Inspection :*
11/10/2011 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
1) OK STUD FRAME WALLS
11/15/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
1) DUCT ABOVE HARD LIDS OK TO COVER
11/15/2011 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
11/17/2011 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
11/22/2011 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
12/05/2011 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
1) PROVIDE SESMIC RESTRAINTS ON RETURN CANS
2) DUCT ABOVE CEILING OK TO COVER
12/05/2011 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
1) SUPPORT EMT 3' OF BOXES
2) SUPPORT ELECTRICAL PER 300.11
3) WHERE IS NL FIXTURE ?
4) ALL EQUIPMENT TO BE LISTED AND LABELED
5) OK TILE AFTER CORRECTIONS, WILL CHECK AT FINAL
12/05/2011 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
12/19/2011 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1) PARALLEL CONDUCTORS TO BE EQUAL IN LENGTHS
2) NEED CABLE BRACING LINE SIDE
3) CANNOT STACK LUGS
4) SERVICE NIPPLE/RACEWAYS TO BE BONDED 250.92
5) NEED FUSES AND "R" PINS INSTALLED
6) FINISH PULL TO TEP
7) FINISH SUB PANELS
8) FOR TEMP POWER DEVICES 8' AND DOWN NEED TO BE INSTALLED
12/21/2011 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
12/21/2011 TEP CLEARANCE - AM JWEATHER Approved TMPP CLEARED FOR #111 PER R. HOLLANDER
01/27/2012 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
02/03/2012 RIGHT OF WAY - FINAL P.Whiddon Approved
02/06/2012 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
1) CHANGES DRAWN IN BY THE HEALTH DEPT. NEED CITY PLAN REVIEW, AS WASTE WATER FEES MAY NEED TO BE ADDED
2) METHOD OF STERILIZATION
3) CLEAN BACTERIA REPORT
02/06/2012 ENGINEERING - FINAL MRUSSO Approved
02/06/2012 SIGN - FINAL MRUSSO Approved
02/06/2012 NPPO - FINAL MRUSSO Approved
02/06/2012 LANDSCAPE - FINAL MRUSSO Approved
02/15/2012 MECHANICAL - HYDRONIC PIPING MRAMBER Approved IVRS - Inspection :*
02/28/2012 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
02/28/2012 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
02/28/2012 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection :*
03/02/2012 HEALTH DEPT - FINAL 724-7908 NRAMIREZ Approved
03/08/2012 FIRE - FINAL WMOTTO Approved
03/08/2012 FIRE SPKLR - FINAL WMOTTO Approved
03/09/2012 CERTIFICATE OF OCCUPANCY JBURGE Approved IVRS - Inspection :*
03/09/2012 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*

Documents

File Name Document Type  
C OF O_03-20-2012.TIF CERT OF OCC VIEW
001_C1.TIF CONSTRPLANS VIEW
002_A1.TIF CONSTRPLANS VIEW
003_A2.TIF CONSTRPLANS VIEW
004_A3.TIF CONSTRPLANS VIEW
005_A4.TIF CONSTRPLANS VIEW
006_A5.TIF CONSTRPLANS VIEW
007_M1.TIF CONSTRPLANS VIEW
008_M2.TIF CONSTRPLANS VIEW
009_P1.TIF CONSTRPLANS VIEW
010_P2.TIF CONSTRPLANS VIEW
011_P3.TIF CONSTRPLANS VIEW
012_E0.0.TIF CONSTRPLANS VIEW
013_ED1.0.TIF CONSTRPLANS VIEW
014_E1.0.TIF CONSTRPLANS VIEW
015_E2.0.TIF CONSTRPLANS VIEW
016_E3.0.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW