Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/19/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PARALLEL CONDUCTORS TO BE EQUAL IN LENGTHS 2) NEED CABLE BRACING LINE SIDE 3) CANNOT STACK LUGS 4) SERVICE NIPPLE/RACEWAYS TO BE BONDED 250.92 5) NEED FUSES AND "R" PINS INSTALLED 6) FINISH PULL TO TEP 7) FINISH SUB PANELS 8) FOR TEMP POWER DEVICES 8' AND DOWN NEED TO BE INSTALLED |