Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM01643
Parcel: 11520001N

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01643
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2011 BILL BALAK ZONING REVIEW Approved
05/31/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the condensate is to be drained from the coolers and from the split-system.
2. Provide a design for the mill room exhaust.
3. Provide a design for the boiler flue.
4. Ensure that the restroom exhaust fans operate when the office HVAC is running.
05/31/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
05/31/2011 ROBERT SHERRY WATER REVIEW Approved
05/31/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/31/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The wash and rinse compartments for the 3-compartment sink shall be directly-connected to the sanitary drain system.
2. Provide a floor drain near the boiler.
3. Provide a note specifying the piping material, insulation, and support for the piping for the boiler.
05/31/2011 DAVE MANN FIRE REVIEW Approved
05/31/2011 RONALD BROWN ADA REVIEW Passed
05/31/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/08/2011 DROBEY1 WWM REVIEW Needs Review
06/08/2011 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2011 DELMA ROBEY OUT TO CUSTOMER Completed