Permit: T08CM02567
Permit Details
Apply Date:
07/25/2008
Applicant:
N/A
Description:
TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
Contractors:
- BRAMS ELECTRIC INC
Permit Reviews
Permit Number - T08CM02567
Permit Status: Final
Permit Description: TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/25/2008 | COMMERCIAL TI | 08/25/2008 | COMPLETED |
| 08/25/2008 | COMMERCIAL TI | 08/25/2008 | COMPLETED |
| 08/25/2008 | OTHER | 09/02/2008 | COMPLETED |
| 09/05/2008 | OTHER | 10/03/2008 | COMPLETED |
| 10/14/2008 | REVISION - - 1ST | 10/28/2008 | COMPLETED |
| 12/02/2008 | REVISION - - 2ND | 12/02/2008 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T08CM02567
Permit Description: TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
Total Completed Inspections - 20
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2008 | FRAMING | JBURGE | Approved | IVRS - Inspection :* |
| 11/03/2008 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* PLYWOOD SHEATHING THROUGHOUT |
| 11/05/2008 | ELECTRIC - UNDERGROUND | RMORENO | Approved | |
| 11/18/2008 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* 1. BOND JUMPERS TO BE SIZED PER 250.102 & 250.66 2. A BOND WILL NEED TO BE POSTED FOR POWER 3. NEED APPROVED PLAN DETAIL PER 480 - BATTERIES |
| 11/18/2008 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
| 11/25/2008 | ELECTRIC - TEMP POWER FOR TEST | RHOLLAND | Approved | IVRS - Inspection :* |
| 11/26/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | TMPP CLEARED PER R. HOLLANDER |
| 12/30/2008 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 12/30/2008 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 12/30/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) CONDENSORS NOT FUSED CORRECTLY 2) PROVIDE SECONDARY DRAINS OR OVERFLOW SENSORS ON FAN COILS 3) CONNECT OVERFLOW SENSORS OR CONDENSATE PUMPS |
| 12/30/2008 | NPPO - FINAL | ACONNOR | Approved | N/A |
| 12/30/2008 | LANDSCAPE - FINAL | ACONNOR | Approved | N/A |
| 12/30/2008 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 12/30/2008 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/30/2008 | FIRE - FINAL | LTHOMAS | Approved | |
| 12/31/2008 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 03/20/2009 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/20/2009 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/20/2009 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | IVRS - Inspection :* |
| 10/25/2015 | BUILDING - FINAL | JBURGE | Approved |