Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address:
4980 N 1ST AV
Address NEW:
4980 N 1ST AV
Apply Date:
07/25/2008
Applicant:
N/A
Description:
TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
Contractors:
  • BRAMS ELECTRIC INC

Permit Reviews

Permit Number - T08CM02567
Permit Status: Final
Permit Description: TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
Start Date Submittal Complete Date Status  
07/25/2008 COMMERCIAL TI 08/25/2008 COMPLETED Review Details
08/25/2008 COMMERCIAL TI 08/25/2008 COMPLETED Review Details
08/25/2008 OTHER 09/02/2008 COMPLETED Review Details
09/05/2008 OTHER 10/03/2008 COMPLETED Review Details
10/14/2008 REVISION - - 1ST 10/28/2008 COMPLETED Review Details
12/02/2008 REVISION - - 2ND 12/02/2008 COMPLETED Review Details

Completed Inspections

Permit Status: Final
Permit Number: T08CM02567
Permit Description: TI: MINI STORAGE TO EQUIP ROOM FOR AT&T
Total Completed Inspections - 20
Date Description Inspector Results Comments
10/30/2008 FRAMING JBURGE Approved IVRS - Inspection :*
11/03/2008 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
PLYWOOD SHEATHING THROUGHOUT
11/05/2008 ELECTRIC - UNDERGROUND RMORENO Approved
11/18/2008 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
1. BOND JUMPERS TO BE SIZED PER 250.102 & 250.66
2. A BOND WILL NEED TO BE POSTED FOR POWER
3. NEED APPROVED PLAN DETAIL PER 480 - BATTERIES
11/18/2008 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
11/25/2008 ELECTRIC - TEMP POWER FOR TEST RHOLLAND Approved IVRS - Inspection :*
11/26/2008 TEP CLEARANCE - AM JWEATHER Approved TMPP CLEARED PER R. HOLLANDER
12/30/2008 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
12/30/2008 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
12/30/2008 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) CONDENSORS NOT FUSED CORRECTLY
2) PROVIDE SECONDARY DRAINS OR OVERFLOW SENSORS ON FAN COILS
3) CONNECT OVERFLOW SENSORS OR CONDENSATE PUMPS
12/30/2008 NPPO - FINAL ACONNOR Approved N/A
12/30/2008 LANDSCAPE - FINAL ACONNOR Approved N/A
12/30/2008 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
12/30/2008 FIRE SPKLR - FINAL LTHOMAS Approved
12/30/2008 FIRE - FINAL LTHOMAS Approved
12/31/2008 ENGINEERING - FINAL MRUSSO Approved
03/20/2009 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
03/20/2009 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :*
03/20/2009 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection :*
10/25/2015 BUILDING - FINAL JBURGE Approved

Documents

File Name Document Type  
STRUCTURALANALYSISREPORT.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW
001__T-1.TIF CONSTRPLANS VIEW
002__G-1.TIF CONSTRPLANS VIEW
003__G-2.TIF CONSTRPLANS VIEW
004__G-3.TIF CONSTRPLANS VIEW
005__C-1.TIF CONSTRPLANS VIEW
006__C-2.TIF CONSTRPLANS VIEW
007__C-3.TIF CONSTRPLANS VIEW
008__E-1.TIF CONSTRPLANS VIEW
009__E-2.TIF CONSTRPLANS VIEW
010__E-3.TIF CONSTRPLANS VIEW
011__E-4.TIF CONSTRPLANS VIEW
012__E-5.TIF CONSTRPLANS VIEW
013__M-1.TIF CONSTRPLANS VIEW
014__M-2.TIF CONSTRPLANS VIEW
015__S-1.TIF CONSTRPLANS VIEW
001__E-4A.TIF CONSTRPLANS VIEW