Permit Number: T08CM02567
Parcel: 10816008B

Address:
4980 N 1ST AV

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM02567
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02567 9/5/08

1. According to the fault calculations, the gutter is 130' from the meter and service disconnect. This is not shown on the plans.
2. New meter and disconnect barely legible on Sheet E-4.
3. Conduit to Panels A1 and A2 appears to originate at the new service disconnecting means on Sheet E-1, but according to the line diagram on Sheet E-4 these conduits originate at a gutter. Please locate the gutter on the plans such that the distances used in the fault calculations are verifiable.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2008 SUE REEVES APPROVAL SHELF Completed
10/03/2008 DELMA ROBEY OUT TO CUSTOMER Completed