Permit Number: T08CM02567
Parcel: 10816008B

Address:
4980 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02567
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2008 STEVE SHIELDS ZONING REVIEW Approved
08/25/2008 RBROWN1 ADA REVIEW Passed
08/25/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02567 8/25/08

1. Please provide sizing for the Main Bonding Jumper, per the requirements of NEC 250.28 (D).
2. Please note that TEP publishes an available fault current of 75,100A for a 1200A, 3-phase, 120/208V service.
3. Distance to power company transformer scales out to be about 111', not 150.
08/25/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/25/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/25/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved