Permit: T08CM02567

Parcel: 10816008B


Addresses:

4980 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/20/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BOND JUMPERS TO BE SIZED PER 250.102 & 250.66
2. A BOND WILL NEED TO BE POSTED FOR POWER
3. NEED APPROVED PLAN DETAIL PER 480 - BATTERIES
11/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 90 DEG. AT SERVICE
OK CONDUIT RUN TO SWITCH ROOM