Apply Date:
03/28/2008
Applicant:
WITMER, GALLAGHER
Description:
NEW SHELL BLDG
Contractors:
- TL ROOF AND ASSOCIATES
Permit Reviews
Permit Number - T08CM01024
Permit Status: Final
Permit Description: NEW SHELL BLDG
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/02/2011 | REVISION - - 4TH | 02/02/2011 | COMPLETED |
02/02/2011 | REVISION - - 4TH | 03/30/2011 | COMPLETED |
03/28/2008 | PLANS OK TO SUBMIT - 3RD PARTY | 03/28/2008 | COMPLETED |
03/28/2008 | 3RD PARTY REVIEW-COMMERCIAL | 05/02/2008 | COMPLETED |
05/02/2008 | POST 3RD PARTY REVIEW | 05/13/2008 | COMPLETED |
05/11/2011 | REVISION - - 5TH | 05/12/2011 | COMPLETED |
05/12/2009 | 3RD PARTY REVIEW-REVISION/OTHER | 05/26/2009 | COMPLETED |
05/20/2009 | REVISION - - 1ST | 05/26/2009 | COMPLETED |
06/11/2010 | REVISION - - 2ND | 06/11/2010 | COMPLETED |
06/23/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 06/23/2008 | COMPLETED |
09/19/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 09/23/2008 | COMPLETED |
10/30/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 10/31/2008 | COMPLETED |
11/04/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 11/10/2008 | COMPLETED |
11/28/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 12/08/2008 | COMPLETED |
12/21/2010 | REVISION - - 3RD | 01/31/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM01024
Permit Status: Final
Permit Description: NEW SHELL BLDG
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
03/28/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08CM01024
Permit Description: NEW SHELL BLDG
Total Completed Inspections - 46
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2008 | ELECTRIC - UFER | LHANLY | Approved | IVRS - Inspection :* 3/0 CU CLAMPED TO 20' REBAR RELOCATED TO BETWEEN GRIDLINE 6 & 7 ON WEST SIDE OF BUILDING PER NOT YET APPROVED REVISION |
07/02/2008 | EXCAVATION/LAYOUT REBAR & ZON | MHENSON | Approved | IVRS - Inspection :* OK TO POUR DUMPSTER FOOTINGS WITH SPECIAL |
07/23/2008 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* OK U.G POWER & DATA TO PHONE ROOM AND TO SWITCH GEAR AREA, FROM SUITE AREA |
08/26/2008 | PLUMBING - YARD WTR LINE/TEST | RLEDONNE | Approved | IVRS - Inspection :* 1. YARD WATER PER HIGHLIGHT ON PAGE P-1 2. TEST ON ROOF DRAIN STUB UP AT BUILD AND 5' FROM BUILDING TEST OK |
10/01/2008 | BUILDING PRE-SLAB | MHENSON | Approved | IVRS - Inspection :* NEED PLUMBING PRE-SLAB |
10/02/2008 | PLUMBING - PRE SLAB | RMYERS | Approved | IVRS - Inspection :* PUBLIC RESTROOMS AND ADJOINING MECHANICAL ROOM OK FOR CONCRETE S.T.O.I |
10/07/2008 | SITE - SEWER | RLEDONNE | Approved | IVRS - Inspection :* |
11/04/2008 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* VENDOR SHED OK |
11/12/2008 | PLUMBING - ROUGH, SOIL | RLEDONNE | Approved | IVRS - Inspection :* NEW 2" GREASE WASTE AND 3" WASTE #113 VENDOR AND #112 - 3" NEW WASTE TEST OK |
11/13/2008 | REINFORCED MASONRY PRE-GROUT | MHENSON | Approved | IVRS - Inspection :* 1. RM. 103 TOP OUT AND 102 GABLE ENDS DETAIL SK33 2. NEED DOCUMENTATION FROM SPECIAL INSPECTOR FOR GABLE ENDS RM. 102 |
11/14/2008 | STUCCO MESH | MHENSON | Approved | IVRS - Inspection :* WEST EXTERIOR WALL GABLE END AND SERVICE ENTRY OK TO STUCCO |
12/01/2008 | FRAMING | MHENSON | Approved | IVRS - Inspection :* PARTIAL - BATHROOMS |
12/09/2008 | STEM WALL/RETAINING WALL | MHENSON | Approved | IVRS - Inspection :* 1. D-3 TO 7 7-D TO E STOREFRONT STEM WALL 2. ADDED STOREFRONT NOT ON PLAN 3. NEED REVISED PLANS FOR STOREFRONT |
12/19/2008 | ROOF NAILING | MHENSON | Approved | IVRS - Inspection :* RM. 102, 103B OK TO DRY IN |
06/16/2010 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
06/21/2010 | PLUMBING - INTERMEDIATE | RLEDONNE | Approved | IVRS - Inspection :* 1) FLUSH VALVES FOR WATER CLOSETS IN WALLS OK |
06/25/2010 | BUILDING - FINAL | MHENSON | Approved | IVRS - Inspection :* 1) RESTROOMS NEED TO BE ACCESSIBLE |
07/08/2010 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* 1) SUPPORT CONDUITS ABOVE PANEL "HP-2" 2) INSTALL ARC FLASH LABELS 3) SUPPORT CONDUITS WITHIN 2' OF PANELS AND SERVICE 4) NEED LOCK NUT OR METAL BUSHING TO SECURE FITTING AT PANEL HP 5) FINISH PAD UNDER SES 6) NEED PLAN REVISION FOR PANLE 'PV'-BEING FED FOR 80 AMPS, PLAN CALLS FOR 60 AMPS 7) NOTE: 408.4 WILL APPLY 8) NEED ADDRESS LABEL OUTSIDE OF SERVICE 9) RECEIVED LETTERS FOR NM CABLE AND TORQUE |
07/08/2010 | ELECTRIC - TEMPORARY SERVICE | RHOLLAND | Approved | IVRS - Inspection :* |
07/08/2010 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | IVRS - Inspection :* |
07/09/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TMPP CLEARED FOR 'HOUSE PANEL' PER R. HOLLANDER-2ND TIME SENT TO TEP |
09/01/2010 | FIRE - FINAL | LThomas | Approved | Approved 9/1/10 |
12/15/2010 | PLUMBING - FINAL | RLEDONNE | Approved | IVRS - Inspection :* 1) GAS PIPING TO #DH1 AND VH#1 & 2 PSI TEST OK (ONLY) |
12/15/2010 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | IVRS - Inspection :* |
12/15/2010 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
12/16/2010 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* 1) FLUE PIPING AT RESTROOMS OK |
01/31/2011 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
01/31/2011 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
01/31/2011 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
01/31/2011 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
01/31/2011 | BUILDING ABOVE CEILING | MHENSON | Approved | IVRS - Inspection :* |
04/05/2011 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* |
04/25/2011 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :* |
04/25/2011 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* |
04/25/2011 | PLUMBING - BACK WATER VALVE | RRICH | Approved | IVRS - Inspection :* |
04/25/2011 | PLUMBING - SEWER HCS CONNECT | RRICH | Approved | IVRS - Inspection :* |
05/09/2011 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* C/O ONLY |
05/09/2011 | NPPO - FINAL | JFEMLING | Approved | Approved |
05/09/2011 | LANDSCAPE - FINAL | JFEMLING | Approved | Approved |
05/09/2011 | RIGHT OF WAY - FINAL | M.Otero | Approved | |
05/10/2011 | OUTDOOR LIGHTING FINAL | DSANTACR | Approved | IVRS - Inspection :* |
05/10/2011 | ELECTRIC - OUTDOOR LIGHTING | DSANTACR | Approved | IVRS - Inspection :* |
05/10/2011 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
05/10/2011 | ENGINEERING - FINAL | JFEMLING | Approved | Remove roll off dumpster, potta john and construction materials prior to last TI C of O for this shell. |
05/11/2011 | PERMIT FINALED | JWEATHER | Approved | |
05/11/2011 | U VALUE FOR WINDOW | LHANLY | Approved |