Permit: T08CM01024

Parcel: 116206290

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T08CM01024

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
01/31/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING ALL OUTLETS LIGHTING AND EXTERIOR EM LIGHTS
2) FESTOON LIGHTING USING EXTENSION CORDS AS PERMANENT WIRING 400.7 & 8
3) TRACK LIGHT CORD AND PLUG FOR PERMANENT WIRING
4) MISSING COVER PLATES
5) LOOSE FITTINGS AT BOXES
6) BOXES AT COMBUSTIBLES 314.20 AND MORE THAN 1/4"
7) EXIT SIGN NOT WORKING
8) LIGHTING CONTRACTOR #2-REDUCING WASHER BACKWARDS AND GROUND BOX LABEL CONTACTOR
9) MISSING BATHROOM LIGHTS
10) FRONT CHANDALIER NOT LISTED, (MADE IN MEXICO) OPEN SPLICES NO GROUND CONDUCTOR
11) STAIRWELL NOT COMPLETED
12) LABEL ROOF DISCONNECTS
13) STILL NEED REVISED PV PLANS AND PV NOT INSTALLED
06/25/2008 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
3/0 CU CLAMPED TO 20' REBAR

RELOCATED TO BETWEEN GRIDLINE 6 & 7 ON WEST SIDE
OF BUILDING PER NOT YET APPROVED REVISION