Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T08CM01024
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
01/31/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING ALL OUTLETS LIGHTING AND EXTERIOR EM LIGHTS 2) FESTOON LIGHTING USING EXTENSION CORDS AS PERMANENT WIRING 400.7 & 8 3) TRACK LIGHT CORD AND PLUG FOR PERMANENT WIRING 4) MISSING COVER PLATES 5) LOOSE FITTINGS AT BOXES 6) BOXES AT COMBUSTIBLES 314.20 AND MORE THAN 1/4" 7) EXIT SIGN NOT WORKING 8) LIGHTING CONTRACTOR #2-REDUCING WASHER BACKWARDS AND GROUND BOX LABEL CONTACTOR 9) MISSING BATHROOM LIGHTS 10) FRONT CHANDALIER NOT LISTED, (MADE IN MEXICO) OPEN SPLICES NO GROUND CONDUCTOR 11) STAIRWELL NOT COMPLETED 12) LABEL ROOF DISCONNECTS 13) STILL NEED REVISED PV PLANS AND PV NOT INSTALLED |
|
06/25/2008 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 3/0 CU CLAMPED TO 20' REBAR RELOCATED TO BETWEEN GRIDLINE 6 & 7 ON WEST SIDE OF BUILDING PER NOT YET APPROVED REVISION |