Permit: T08CM01024

Parcel: 116206290

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01024

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/31/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/08/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT CONDUITS ABOVE PANEL "HP-2"
2) INSTALL ARC FLASH LABELS
3) SUPPORT CONDUITS WITHIN 2' OF PANELS AND SERVICE
4) NEED LOCK NUT OR METAL BUSHING TO SECURE FITTING AT PANEL HP
5) FINISH PAD UNDER SES
6) NEED PLAN REVISION FOR PANLE 'PV'-BEING FED FOR 80 AMPS, PLAN CALLS FOR 60 AMPS
7) NOTE: 408.4 WILL APPLY
8) NEED ADDRESS LABEL OUTSIDE OF SERVICE
9) RECEIVED LETTERS FOR NM CABLE AND TORQUE
06/25/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROJECT TO BE DONE FOR TESTING
2) STILL NEED TORQUE LETTER
3) NEW CONSTRUCTION OUT OF GROUND
4) NEED BOND FOR TEMP POWER
06/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PHYSICAL PROTECTION FOR NM CABLES
WAITING ON COPY OF APPROVAL FOR NM CABLE
NEED LETTER OF TORQUE ON COMPANY LETTERHEAD
NOTE 408.5, 352.46, 300.4
06/08/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ANSWERED QUESTIONS REGARDING NM CABLE-PHYSICAL PROTECTION ?
2) GUTTER USAGE-366
3) OK RACEWAYS FOR FIRE ALARM
4) OK WALL AND HARD LIDS BATHROOMS
05/20/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) JUNCTION BOXES TO BE ACCESSIBLE
2) PLEASE PROVIDE LETTER AUTHORIZING USE OF 1/2" EMT AND NM CABLE
3) SECURE NM CABLE TO BOXES 315.5 (C)
4) PROVIDE PHYSICAL PROTECTION FOR NM CABLE 300.4
5) NO MORE THAN 360 DEGREE IN CONDUIT RUNS
6) OK INTERIOR BLOCK WALLS ROOMS 101-108
7) OK PVC CONDUIT AS SES PAD
408.3 & 352.46 WILL APPLY