Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T08CM01024
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
01/31/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED SUPPORT ON ALL PIPING FOR SOLAR WATER HEATER 2) COMPLETE INSTALL OF BACKWATER VALVES 3) MAKE ALL CLEANOUTS WATER AND GAS TIGHT 4) CALL ALL ACTIVITY FOR HISTORY 5) LIST MAY NOT BE COMPLETE |
|
04/01/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DRY WELL FOR WATER COOLER PER REDLINE TO BE APPROVED BY CITY OF TUCSON - UNDERGROUND OK 2' PVC AND 1/2 COPPER |
|
11/12/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* NEW 2" GREASE WASTE AND 3" WASTE #113 VENDOR AND #112 - 3" NEW WASTE TEST OK |
|
08/14/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* TEST ON 6" PVC FROM STAIRWELL NOT PER PLAN TEST ON INSTALL PER PLAN |
|
07/25/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST 4" FLOOR DRAIN IN TRASH ROOM PER REDLINE PAGE P1 INITIAL |
|
07/23/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. UNDERGROUND PVC FOR PUBLIC RESTROOMS OK 2. 2" MOP SINK TIED INTO G.W OK WATER TEST OK OK TO COVER |
|
06/12/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | 1. 2 - 4" VENTS ADDED DOWNSTREAM OF BACKWATER VALVES 2. INTERCEPTOR INSTALLED OK - OK TO COVER 3. OK TO COVER SEWER P.O.C AT RESTROOMS #106 & #108 |
|
06/06/2008 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* BUILDING SEWER DOWNSTREAM OF BACKWATER VALVE TO BE VENTED PER 904.1 2006 UPC |
|
05/30/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PER HIGHLIGHT ON P-1 |
|
05/28/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PER HIGHLIGHTER ON PAGE P-1 |
|
05/27/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. FROM A+ TO 4.5 GREASE TRAP PIPING TEST OK 2. 4.5 TO 8 TEST OK |
|
05/23/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" GW FOR EAST SECTION PER INITIAL P.1 WATER TEST OK |
|
05/22/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) PER HIGHLIGHT ON PAGE P-1 |