Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3609 E 5TH ST
Address NEW:
3609 E 5TH ST
Apply Date:
02/21/2007
Applicant:
VERONICA SCOTT
Description:
ELECTRIC SERVICE UPGRADE TO 400AMP

Permit Reviews

Permit Number - T07EL00318
Permit Status: Expired
Permit Description: ELECTRIC SERVICE UPGRADE TO 400AMP
Start Date Submittal Complete Date Status  
02/21/2007 ELECTRICAL 02/21/2007 COMPLETED Review Details
04/18/2007 ELECTRICAL 04/23/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL00318
Permit Status: Expired
Permit Description: ELECTRIC SERVICE UPGRADE TO 400AMP
Total Outstanding Activity Conditions - 1
Date Name
02/21/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL00318
Permite Description: ELECTRIC SERVICE UPGRADE TO 400AMP
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
03/26/2007 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DESCRIPTION OF WORK DOES NOT MATCH WHAT IS DONE. PERMIT CALLS FOR 200 AMP SERVICE-400 AMP INSTALLED
2) GROUND RODS NEED TO BE 6' APART PER NEC 250.5.3
3) GROUND RODS CANNOT BE BENT OVWER
4) SECURE SERVICE RISER TO BLDG
5) 400 AMP SERVICE REQUIRES APPROVED SET OF DRAWINGS
6) PLEASE EXPLAIN WHAT OLD DISCONNECT IS BEING USED FOR
7) CHASE NIPPLE NOT LISTED FOR CONDUIT CONNECTOR-USE LISTED CONNECTOR
03/26/2007 ELECTRIC - CABLE DROP N/A Denied
03/26/2007 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/16/2007 ELECTRIC - FINAL N/A Partial Approval OK TO CLEAR SERVICE INCREASE
WILL NOTIFY TEP

ONCE SERVICE CHANGED OVER & FINALED
CALL FOR FINAL INSPECTION

Completed Inspections

Permit Status: Expired
Permit Number: T07EL00318
Permit Description: ELECTRIC SERVICE UPGRADE TO 400AMP
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/16/2007 TEP CLEARANCE - PM JWEATHER Approved INCR CLEARED PER R. MAJUTA

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW