Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2007 | ELECTRIC - FINAL | Partial Approval | OK TO CLEAR SERVICE INCREASE WILL NOTIFY TEP ONCE SERVICE CHANGED OVER & FINALED CALL FOR FINAL INSPECTION |
|
| 05/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER AND GAS PIPING BOND REQUIRED PER NEC 2002 250-104A-METAL WATER PIPING AND 250-104 B-METAL GAS PIPING 2) PLAN ON SITE DOES NOT STATE REMOVE WATER AND GAS BOND IT STATE "REMOVE N-G BOND" MEANING REMOVE NEUTRAL AND GROUND BOND AT OLD SERVICE |
|
| 04/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #3 GROUND RODS CANNOT BE BENT #7 CHASE NIPPLE NOT LISTED FOR CONDUIT CONN. #8 LAST INSPECTOR DID NOT LIST A REQUIREMENT FOR A WATER & GAS LINE BOND. THEY WILL NEED TO BE INSTALLED |