Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DESCRIPTION OF WORK DOES NOT MATCH WHAT IS DONE. PERMIT CALLS FOR 200 AMP SERVICE-400 AMP INSTALLED 2) GROUND RODS NEED TO BE 6' APART PER NEC 250.5.3 3) GROUND RODS CANNOT BE BENT OVWER 4) SECURE SERVICE RISER TO BLDG 5) 400 AMP SERVICE REQUIRES APPROVED SET OF DRAWINGS 6) PLEASE EXPLAIN WHAT OLD DISCONNECT IS BEING USED FOR 7) CHASE NIPPLE NOT LISTED FOR CONDUIT CONNECTOR-USE LISTED CONNECTOR |